Specifications

8 - ZONE INFORMATION
Digital Monitoring Products XR6/XR10 Programming Guide
16
8.11 ENTRY DELAY
Select the entry delay timer for this zone. Entry delay timers 1 and 2 are
programmed in section 6.4 Entry Delay 1.
8.12 CROSS ZONE
Select YES to enable cross zoning for this zone. Cross zoning requires this zone to
trip twice, or this zone and another cross zoned zone to trip, within a
programmed time before an alarm report is sent to the receiver.
When a cross zoned zone trips, the bell and Output action assigned to the zone
activates. See section 7.4 Bell Action. The cross zone time specified in System
Options begins to count down. See section 6.6 Cross Zone Time. If another cross
zoned zone in the system faults, or if the first zone restores and faults again
before the cross zone time expires, the panel sends an alarm report.
If no other cross zoned zone in the system trips before the cross zone time
expires, the panel sends only a fault report from the first zone to the receiver.
Cross zoning is not compatible with Fire Verify zone types: You cannot enable cross zoning for Fire Verify zones.
8.13 PRIORITY
Selecting YES allows you to provide additional protection for a zone by requiring it
to be in a normal condition before its assigned area can be armed. A priority zone
cannot be bypassed.
A Priority zone must be in a normal condition before it can be armed. If a user
attempts to arm the area, the keypad displays the bad zone name followed by
PRIORITY ZONE and the arming is stopped.
8.14 ZONE NUMBER
Enter the zone number you want to program next. Return to section 8.1 and
follow the descriptions of each programming prompt. If all zones are programmed,
press the Back Arrow key at the ZONE NO: – display to continue.
PRIORITY NO YES
ZONE NO: –
CRS ZONE NO YES
ENTRY DELAY: 1