Specifications

8 - ZONE INFORMATION
Digital Monitoring Products XR6/XR10 Programming Guide
14
8.6 ARM AREAS
This option specifies the areas to be armed by the Arming Type Zone. When
disarmed, all areas in the system are disarmed.
PERIMETER/ALL - Specify whether the arming zone arms just the Perimeter
(PERIM) or the Perimeter and Interior areas (ALL) for All/Perimeter systems.
HOME/SLEEP/AWAY - Specify whether the arming zone arms the Perimeter
(HOME), the Perimeter and Interior (SLEEP), or all three areas (AWAY).
Arming zone operation
If a bad (faulted) Priority zone is in the area being armed by an Arming zone, the arming is stopped. If there are no
Priority zones, or they are all in a normal condition, the following applies:
If a non-Priority zone is in a bad condition when an area is armed with a keyswitch on an Arming zone, the arming is
delayed for five seconds. If, during the five-second delay, the keyswitch is turned to disarm, the arming is stopped. If
the keyswitch is held in the arming position for the full five seconds, the bad zone is force armed and the area
armed.
Momentary keyswitch operation
When the Arming zone changes from normal to short, any armed areas are disarmed. If all areas are disarmed when
the Arming zone is shorted, the panel arms all areas. When the Arming zone changes from normal to open while any
areas are armed, an alarm is indicated and the areas must be disarmed from a keypad. If all areas are disarmed, only
a trouble is indicated.
8.7 NEXT ZONE
When YES is selected, the programming for the zone terminates and the display
returns to ZONE NO: - allowing you to enter a new zone number. To make changes
to the Alarm Action for a zone, answer the NEXT ZONE? prompt with NO. The
Alarm Action is then defined in sections 8.8 through 8.13.
8.8 ALARM ACTION
The Alarm Action section allows you to change or confirm the default alarm
characteristics of a zone type that was selected in section 8.4 Zone Type.
If you selected the non-24-hour zone type—Blank, Night, Day, Exit, Auxiliary 1, or
Auxiliary 2— the Alarm Action programing begins with Disarmed Open.
If you selected the 24-hour zone type—Fire, Panic, Emergency, or Supervisory—the
Alarm Action programming begins with Armed Open.
The Fire Verify zone type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone is placed into shorted condition, the panel
performs a Sensor Reset and does not send a report. If any Fire Verify or Fire zone
initiates an alarm within 120 seconds after the reset, an alarm is indicated. If an
alarm is initiated after 120 seconds, the cycle is repeated. If no other Fire Verify
or Fire zone is alarmed within 120 seconds, a zone fault report is sent to the
receiver.
8.9 DISARMED OPEN
Defines the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to define:
Message to Transmit Output Number Output Action
See sections 8.9A to 8.9C. You must also make these selections for the Disarmed
Short, Armed Open, and Armed Short zone conditions.
Press the COMMAND key to continue.
NEXT ZN? NO YES
ALARM ACTION . . . .
DISARMED OPEN
PERIM ALL
HOME SLEEP AWAY
ARM AREAS: