Specifications

7 - OUTPUT OPTIONS
Digital Monitoring Products XR6/XR10 Programming Guide
12
7.5 OUTPUT ACTION
This option allows you to define the operation of the panel's four annunciator
outputs.
7.5A CUTOFF OUTPUTS
Any or all of the available outputs can be programmed here to turn off after the
time specified in OUTPUT CUTOFF TIME. See section 7.5B. To disable this option,
press any Select key to clear the display of output numbers and then press
COMMAND.
7.5B OUTPUT CUTOFF TIME
If a Cutoff Output is assigned in section 7.5A, you can enter a Cutoff Time of up
to 15 minutes for the output to remain on. If the output is turned off manually,
the cutoff time is reset. The Cutoff Time can be from 1 to 15 minutes. Enter zero
to provide continuous output.
The Cutoff Timer is shared by all outputs. If a second output trips, the timer is not
reset. Both outputs turn off when the original time expires.
7.5C COMMUNICATION FAILURE OUTPUT
This output is turned on when a DD, 4-2, or CID system fails to communicate with
the receiver after three successive dial attempts. Enter zero to disable.
7.5D FIRE ALARM OUTPUT
This output is turned on any time a fire type zone is placed in alarm. The output is
turned off using the Sensor Reset option while no additional fire type zones are in
alarm. Enter zero to disable this output.
7.5E FIRE TROUBLE OUTPUT
This output is turned on any time a fire type zone is placed in trouble or when a
supervisory type zone is placed in alarm or trouble. The output is turned off when
all fire and supervisory troubles are restored to normal. The output is turned off
when a Sensor Reset is performed after a supervisory alarm. Enter zero to disable
this output.
7.5F AMBUSH OUTPUT
This output is turned on any time an Ambush code is entered at a keypad. The
output is turned off using the Sensor Reset option. Enter zero to disable.
7.5G ENTRY OUTPUT
This output is turned on at the start of the entry delay time. The output is turned
off when the area is disarmed or the entry delay time expires. Enter zero to
disable this output.
7.5H EXIT OUTPUT
This output is turned on any time an exit delay time starts and is turned off when
the system arms or when the arming has been stopped. Enter zero to disable.
7.5I READY OUTPUT
This output is turned on whenever all disarmed zones are in a normal state. The
output is turned off when any disarmed zone is in a bad state. Enter zero to
disable this output.
7.5J ARMED OUTPUT
This output is turned on any time an area of the system is armed. The output is
turned off when the system is completely disarmed.
7.5K BURGLARY OUTPUT
This output turns on any time a burglary zone is in alarm. The output is turned off
when the area in which the alarm occurred is disarmed and no other burglary
zones are in alarm.
7.5L GROUND START OUTPUT
This output turns on for 750ms any time the panel seizes the telephone line. Enter
zero to disable this output.
BURGLARY OUT: 0
ARMED OUT: 0
READY OUT: 0
EXIT OUT: 0
ENTRY OUT: 0
AMBUSH OUT: 0
FIRE TRB OUT: 0
FIRE ALR OUT: 0
COM FAIL OUT: 0
CUTOFF TIME: 0
CO OUTS: - - - -
OUTPUT ACTION . . .
GROUND START: 0