Specifications
XR6/XR10 Programming Guide Digital Monitoring Products
11
7 - OUTPUT OPTIONS
7.1 OUTPUT OPTIONS
This function allows you to program the panel's Bell Output functions and certain
Output options. Switched Ground (open collector) outputs are available from the
XR6/XR10 when using a 4-wire output harness (Model 300 Harness). Refer to the
XR6/XR10/XR20/XR40 Installation Guide (LT-0229) for complete information.
A description of each output option follows:
7.2 BELL CUTOFF TIME
Enter the maximum time the Bell Output remains on. If the Bell Output is
manually silenced or the system is disarmed, the cutoff time is reset. The Bell
Cutoff Time can be from 1 to 15 minutes in one minute increments.
Enter zero to provide a continuous bell output.
7.3 AUTOMATIC BELL TEST
When YES is selected, the Bell Output is turned on for two seconds when all areas
in the system are armed. In addition, the Closing Wait feature is activated if
Opening/Closing Reports is YES. See section 5.2 Opening/Closing Reports. The
Bell Test only occurs when the areas are armed from a keypad. Arming performed
from an arming zone or remotely from Remote Link⢠or Remote Access
TM
does not
activate the Bell Test.
Closing Wait operation
Closing Wait provides a delay time before a monitored system arms until the panel receives an acknowledgment of
the closing report from the central station receiver. During the delay, the keypad displays DIALING . . .. Once the
closing is acknowledged, the keypad buzzer and the Bell Output sound for two seconds and the keypad displays the
system armed message.
If the closing report is not acknowledged, the keypad buzzer sounds and Bell Output does NOT sound, the keypad
displays LOCAL ALARM ONLY, and the system arms locally.
7.4 BELL ACTION
This option defines the type of Bell Output for zone alarms. (Trouble conditions do
not activate the Bell Output.) There are seven zone types you can program for Bell
Output.
For a steady Bell Output, enter S. For a pulsed output, enter P. For a Temporal
Code 3 output enter T. For no Bell Output, enter N. Program the bell action for
each zone type below:
7.4A FIRE ZONES
Defines Bell Action for Fire Type Zones.
7.4B BURGLARY ZONES
Defines Bell Action for Burglary Type zones. If you select N, Exit Error alarms are
not indicated locally but Exit Error reports are still sent to the receiver. See
Appendix section 11.2 False Alarm Reduction Features.
7.4C SUPERVISORY ZONES
Defines Bell Action for Supervisory Type Zones
7.4D PANIC ZONES
Defines Bell Action for Panic Type Zones
7.4E EMERGENCY ZONES
Defines Bell Action for Emergency Type Zones
7.4F AUXILIARY 1 ZONES
Defines Bell Action for Auxiliary 1 Type Zones
7.4G AUXILIARY 2 ZONES
Defines Bell Action for Auxiliary 2 Type Zones
OUTPUT OPTIONS
BELL CUTOFF: 15
BELL TEST NO YES
FIRE TYPE: P
BURGLARY TYPE: S
SUPRVSRY TYPE: N
PANIC TYPE: N
EMERGNCY TYPE: N
AUXLRY I TYPE: N
AUXLRY 2 TYPE: N
BELL ACTION . . . . .