Specifications

XR6/XR10 Programming Guide Digital Monitoring Products
9
5 - SYSTEM REPORTS
5.1 SYSTEM REPORTS
This section of the Programmer allows you to select the reports the panel sends to
the receiver.
5.2 OPENING/CLOSING REPORTS
YES allows the panel to send opening/closing reports by user to the receiver.
5.3 ABORT REPORT
YES allows the panel to send an alarm abort report to the receiver any time an
alarm report has also been sent and the Bell Cutoff time has not expired. See Bell
Cutoff section 7.2. The area must be disarmed and no alarmed zones can still be
armed. A Bell Silenced Report is also sent if the alarm bell is silenced with a valid
user code juring an alarm. When the system is disarming during an alarm, only
Abort and Opening Reports are sent.
5.4 ZONE RESTORAL REPORTS
This option allows you to specify whether the panel sends zone restoral reports
and also when they will be sent.
NO - Restoral reports are not sent by the panel.
YES - The panel always sends zone restoral reports at the time the zone restores
from an alarm or trouble condition.
DISARM - The panel sends zone restoral reports when a zone that has restored
from an alarm or trouble is disarmed. 24-hour zones send restorals immediately.
5.5 BYPASS REPORTS
YES allows the panel to send all zone bypass, reset, and force arm reports to the
receiver. The bypass report includes the zone number, zone name, and the user
number of the individual bypassing the zone.
5.6 CODE CHANGE REPORTS
YES allows the panel to send all code additions, changes, and deletions to the
receiver. The code change report includes the user number added or deleted and
the user number of the individual making the change.
5.7 AMBUSH
YES allows an ambush report to be sent anytime user code number one is entered
at a keypad. Selecting NO disables the ambush report and allows user code
number one to operate the same as all other codes.
SYSTEM REPORTS
RESTORAL: YES
NO YES DISARM
AMBUSH NO YES
BYPASS NO YES
OPN/CLOS NO YES
ABORT NO YES
CODE CHG NO YES