Specifications
2 - INITIALIZATION
Digital Monitoring Products XR6/XR10 Programming Guide
4
2.1 INITIALIZATION
This function allows you to set the panel's user codes and Programmer selections
back to factory defaults before programming the panel for the first time or a new
installation.
After you select YES to clear a section of memory, the panel asks if you are sure
you want to clear the memory. This is a safeguard against accidently erasing the
programming. No memory is cleared from the programming until you answer yes to
the SURE? YES NO prompt.
A description of each initialization options follows below:
2.2 CLEAR ALL CODES
YES clears the panel's user code memory and assigns the Master user code 99 to
user number 12.
2.3 SET TO FACTORY DEFAULTS
YES sets the panel's Programmer selections back to factory defaults and clears any
information stored in Display Events memory.
2.4 HOURS TILL TEST
Enter the number of hours from 0 to 23 the panel waits to send the Recall Test to
the receiver. Entering Zero (0) sends the first recall test report when the
programmer is exited.
Once you have finished programming the panel, reset the panel by shorting the J16
reset jumpers for two seconds. The Recall Test timer now begins and runs the
number of hours programmed in Hours Till Test. After the programmed hours have
elapsed, the Recall Test is sent to the receiver. Whatever time of day this happens
to be is the time that the Recall Test will always be sent according to the number
of days you selected in Test Frequency.
CODES? NO YES
SURE? YES NO
DEFAULTS? NO YES
SURE? YES NO
HRS TILL TEST 12
INITIALIZATION