Installation guide

INSTALLATION
Digital Monitoring Products XR6/XR10 Installation Guide
8
Standby Current Alarm Current
Command Processor Panel 50mA ______ mA 50mA ______ mA
Active Zones 1-9 Qty _____ x 1.6mA ______ mA Qty _____ x *2mA ______ mA
Active Zone 10 (zone 6 on XR6) 4mA ______ mA 30mA ______ mA
2-Wire Smoke Detectors Qty _____ x .1mA ______ mA Qty _____ x .1mA ______ mA
Bell Output 1500mA max. ______ mA
770 and 771 Keypads Qty _____ x 100mA ______ mA Qty _____ x 100mA ______ mA
Active Zones (EOL installed) Qty _____ x 1.6mA ______ mA Qty _____ x *2mA ______ mA
Annunciator (ON) Qty _____ x 20mA ______ mA
690, 790, 791, and 793 Keypads Qty _____ x 100mA ______ mA Qty _____ x 100mA ______ mA
Active Zones (EOL installed) Qty _____ x 1.6mA ______ mA Qty _____ x *2mA ______ mA
692 Keypads Qty _____ x 30mA ______ mA Qty _____ x 70mA ______ mA
710 Bus Splitter/Repeater Qty _____ x 30mA ______ mA Qty _____ x 30mA ______ mA
711 or 714 Zone Expander Qty _____ x 7mA ______ mA Qty _____ x 7mA ______ mA
Active Zones (EOL installed) Qty _____ x 1.6mA ______ mA Qty _____ x *2mA ______ mA
715 Zone Expander Qty _____ x 7mA ______ mA Qty _____ x 7mA ______ mA
Active Zones (EOL installed) Qty _____ x 4mA ______ mA Qty _____ x 30mA ______ mA
2-Wire Smokes Qty _____ x .1mA ______ mA Qty _____ x .1mA ______ mA
714-8 or 714-16 Point Zone Expanders 20mA ______ mA 20mA ______ mA
Active Zones (EOL installed) Qty _____ x 1.6mA ______ mA Qty _____ x *2mA ______ mA
715-8 or 715-16 Point Zone Expanders 20mA ______ mA 20mA ______ mA
Active Zones (EOL installed) Qty _____ x 4mA ______ mA Qty _____ x 30mA ______ mA
2-Wire Smokes Qty _____ x .1mA ______ mA Qty _____ x .1mA ______ mA
733 Wiegand Interface 30mA ______ mA 30mA ______ mA
Active Zones (EOL installed) Qty _____ x 1.6mA ______ mA Qty _____ x *2mA ______ mA
Annunciator (ON) 20mA ______ mA
738A Ademco Wireless Interface 75mA ______ mA 75mA ______ mA
w/Receiver
FA426 16 Point Receiver 50mA ______ mA 50mA ______ mA
Auxiliary Powered Devices on
Terminals 7 and 11 ______ mA ______ mA
(Other than keypads)
Total Standby ___________ mA Total Alarm ____________ mA
Total Standby ____________ mA x number of standby hours needed ______ = ___________ mA/hours
Total Alarm + ___________ mA/hours
Total ___________ mA/hours
x_
.001_____
= ___________ A/hours required
* Based on 10% of active zones
in alarm condition
6.7 XR6/XR10 Standby Battery Calculations