Installation guide
Page 4
Introduction
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR6/XR10/XR20 Installation Guide
Figure 1: XR6/XR10/XR20 wiring diagram
Keypads
Models 670, 770, 771
100mA @ 8 - 16 VDC
125mA with display lit
Models 690, 790,
791, 793
100mA @ 8 - 16 VDC
Model 692
75mA @ 8 -16 VDC
Bell
10.4 - 13.2 VDC
Total current: 1.5 Amps
max. w/ 40 VA
600mA w/20 VA
Household System
An alarm sounding
device must be
installed indoors so that
it is clearly heard in all
sleeping areas.
Bell
DMP transformers:
Model 320
16.5 VAC 40VA
Class 2 wire-in
Model 321
16.5 VAC 40VA
Class 2 plug-in
Model 324
Plug into
120 VAC
outlet not
controlled
by switch.
16 - 18 gauge wire
Cold Water Pipe Earth Ground
Maximum AC wire distance
With 16 gauge wire: 70 feet
With 18 gauge wire: 40 feet
Output Header J11
All outputs must be connected to
devices located within the same room
as the control panel.
Use DMP Model 300 Harness.
Front Tamper
Rear Tamper
Tamper protection when
required for Model 349A
Attack Resistant
Enclosure.
Zone 10 compatibility
identifier: A
Maximum operating range:
8.8 VDC - 14.2 VDC.
See section 11.1 in the XR6/XR10/XR20
Installation Guide (LT-0229) for a list of
approved 2-wire smoke detectors.
Heat detectors, manual pull
stations, or any other shorting
device. Unlimited number of units.
2-wire
smoke
detector
4-wire smoke detector
Power
Supervision
Relay
Up to 500mA auxiliary
current at 10.4 - 13.2
VDC from Terminal 7.
Smoke Output
100mA @ 10.4 - 13.2 VDC
Terminal 11
3.3k Ω
DMP Model 309
Command Processor Reset
Phone Jack Connector
PROG
Programmer Header J8
Use DMP Model 330 Harness
RJ Cable Monitor J7
Use DMP Model 306 Harness
J4
J7
J8
J16
J11
U11
RJ SUP
1
2
3
4
EPROM
Socket
+ -
Smoke
Detector
22 GA. MIN BLACK
22 GA. MIN GREEN
22 GA. MIN YELLOW
22 GA. MIN RED
ZONE 5
ZONE 6
ZONE 4
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 2
ZONE 1
ZONE 3
1K Ω
1K Ω
BLACK
RED
1K Ω
1K Ω
1K Ω 1K Ω
1K Ω
1K Ω
1K Ω
AC AC +B -B BELL GND RED YEL GRN BLK SMK Z1 GND Z2 Z3 GND Z4 Z5 GND Z6 Z7 GND Z8 Z9 Z10+ Z10-
Red
Black
Secondary Power Supply
1.2 Amps max. charging
current. Use only 12 VDC
rechargable batteries. DMP
Model 367. Replace every
3 - 5 years.
XR6 or XR20 only
ZONE EXPANDER
Model 714
15mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
ZONE EXPANDER
Model 715
15mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
AC wiring must be in conduit and exit
out the left side of the panel enclosure
Wiring on
terminals 5 thru
17 must exit to
the right and
maintain a 1/4"
separation from
the AC and
battery positive
wiring.
Detail for XR6 only
See detail below
for XR6 panel only
Z3 GND Z4 Z5 Z6+ Z6-
ZONE 6
ZONE 5
2-wire
smoke
detector
ZONE 4
A B C D E F G H I J K L
V W XM N O P Q R S T U
YZ
COMMAND
SPEC I AL
STAY
INSTAN T
BYPASS CO DE
90
1234
56
7
8
6 7 8 9 10
1 2 3 4 5
INSTANT
STAY
ARMED
TRBL
POWER
READY
16.5 VAC 20VA