Panel Specifications
1.1 Power supply
Transformer Input: 16.5 VAC 40VA (Models 320 wire-in or 321 plug-in)
16.5 VAC 20VA (Model 324 plug-in)
Standby Battery: 12 VDC 7.0Ah (40VA transformer charges up to 2 batteries)
Auxiliary Output: 12 VDC at 500mA
Bell Output: 12 VDC at 1.5 Amps with 40VA transformer, 600mA with 20VA transformer
Smoke Detector Output: 12 VDC at 100mA
All circuits inherent power limited
1.2 Communication
Built-in SDLC Digital Dialer communication to DMP Model SCS-1 Receivers
Built-in 4-2 communication to non-DMP receivers
Built-in M2E (Radionics Modem IIe) communication to non-DMP receivers (XR20 only)
Built-in CID (Contact ID) communication to non-DMP receivers
Either panel can operate as a local system.
1.3 Panel zones
Nine 1k W EOL burglary zones (zones 1 to 9), (zones 1 to 5 on XR6)
One 3.3k W EOL Class B powered fire zone with reset capability (zone 10 on XR10 and XR20), (zone 6 on XR6)
1.4 Keypads
You can connect up to four of the following supervised keypads to the XR6/XR10/XR20 panels.
16 or 32 character alphanumeric keypads
10-zone LED keypads
In addition, the following zone expanders can be added to the XR20 panel:
Four and single point zone expanders
Single point PIR and glassbreak detectors
When using the FA426 Wireless Receiver, the XR20 allows unsupervised devices to be added to address five.
1.5 Outputs
The XR6/XR10/XR20 panels provide four open collector outputs rated for 50mA each. See section 12.1. A Model
300 Wire Harness is required. The open collector outputs provide the ground connection for a positive voltage
source.
1.6 Enclosure specifications
The XR6/XR10/XR20 panel ships in an enclosure with EOL resistors, battery leads, user's guide, and
programming sheet.
Size: 12.5" W x 9.5" H x 2.75" D
Weight: 4 lbs
Color: Gray or Black
Construction: 20 gauge cold rolled steel