Installation guide

Page 18
Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR6/XR10/XR20 Installation Guide
24.1 XR20 Multiple Indicating Circuit Module Installation
AUXILIARY
POWER
SUPPLY
12 or 24 VDC
5 Amp Maximum
Power Supply
Trouble Contacts
N/C
NOTE: If an auxiliary supply is not used,
terminals 3 and 4 on the 866 Indicating
Circuit Module can be jumpered together
to supply bell power from the XR20 panel.
A maximum of 1.5 Amps at 12 VDC is
available from terminal 5 of the XR20.
Each 866 Indicating Circuit Module
in alarm draws up to 35mA from its
terminal 3 alarm input.
AC
1
234
56
78
10 11 12
13
14
15
16
17
18
19
AC +B -B
BELL
GND
SMK
GND
9
RED
YEL
GRN
BLK
20
21
22 23 24 25
26
27 28
L1 L2
GND
GND
GND
GND
L3
L4 L5 L6 L7 L8 L9- L9+ L10- L10+
The Auxiliary Power Supply and Indicating Circuit Module
trouble contact zone must be programmed as a Supervisory
Type zone and must be selected for display in the keypad
status list.
= Supervised Circuit
S
S
S
S
S
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power + Input
Bell Power Ð Input
Bell A + Output -
Bell A Ð Output
Bell B + Output
Bell Trouble
Bell Trouble
Bell B Ð Output
9
10
11
UL Listed, Polarized
Indicating Devices.
Style Z
Notification Circuit Module
DMP Model 865
85mA at 12 VDC
AUXILIARY
POWER
SUPPLY
Power Supply
Trouble Contacts
N/C
12 or 24 VDC
5 Amp Maximum
S
S
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
UL Listed, Polarized
notification Devices.
10k EOL Resistor
DMP Model 308
Notification Circuit Module
DMP Model 866
37mA at 12 VDC
1k
Optional Module installation
Each 865 Notification Circuit Module
in alarm draws up to 85mA from its
terminal 3 alarm input.
S
S
S
S
S
S
S
S
S
S
S
Style W
J16
Command Processor Reset
Phone Jack Connector
EPROM Socket
U11
J11
1
2
3
4
J4
Digital Monitoring Products
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282