Installation guide

Page 15
Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR6/XR10/XR20 Installation Guide
UL 1635 SPECIFICATIONS
Digital Burglar Alarm Communicator System Units
18.1 Digital Dialer telephone number
Both programmed telephone numbers must begin with a D or P. See sections 3.17 and 3.18 of the XR6/XR10
Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).
18.2 Entry delay
The maximum entry delay used must not be more than 60 seconds. See section 6.4 of the XR6/XR10
Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).
18.3 Exit delay
The maximum exit delay used must not be more than 60 seconds. See section 6.5 of the XR6/XR10
Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).
18.4 Test frequency
The Test Frequency option must be programmed so that the panel sends a report once every 24 hours. See
section 3.6 of the XR6/XR10 Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).
18.5 Automatic bell test
This option must be programmed as YES. See section 7.3 of the XR6/XR10 Programming Guide (LT-0230) and
XR20 Programming Guide (LT-0305).
18.6 Grade B Central Station
Grade B Central Station service can be provided under UL 1635 by adding a Grade A local audible signal
appliance and placing the Model XR6/XR10/XR20 panel into the Model 349A Grade A Attack Resistant Housing.
UL 365 and 609 SPECIFICATIONS
Police Station Connected and Local Burglar Alarm Units and Systems
19.1 Entry delay
The maximum entry delay used must not be more than 60 seconds when using the Model 349A Grade A housing.
See section 6.4 of the XR6/XR10 Programing Guide (LT-0230) and XR20 Programming Guide (LT-0305).
19.2 Grade A bell
A Grade A local audible signal appliance must be used.
19.3 Bell cutoff
The bell cutoff time cannot be less than 15 minutes. See section 7.2 of the XR6/XR10 Programming Guide
(LT-0230) and XR20 Programming Guide (LT-0305).
19.4 Automatic bell test
The Automatic Bell Test option must be programmed as YES. See section 7.3 of the XR6/XR10 Programming
Guide (LT-0230) and XR20 Programming Guide (LT-0305).
19.5 Grade A Mercantile
For Grade A Mercantile and Police Station Connect operation the Model XR6/XR10/XR20 must be mounted in a
Grade A attack resistant housing, (DMP Model 349A).
19.6 Mercantile Safe and Vault
When the DMP Model 349A housing is used, the XR6/XR10/XR20 provides operation as a mercantile safe and
vault alarm. Bell Supervision and wiring must be in accordance with UL 681. If the panel is mounted outside the
safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should be
used. The XR6/XR10/XR20 does not provide operation as a Bank Safe and vault alarm.
19.7 Line security for Police Connect
Basic line security is provided when the Model XR6/XR10/XR20 is configured as a dialer system.