Specifications

Digital Monitoring Products XR5 Programming Guide
16
zone inFormaTion
7.9
SWGR BYP: NO YES
Swinger Bypass
YES allows the zone to be bypassed by the panel after three alarm, trouble, or local
trips within one hour. Selecting NO disables swinger bypassing for this zone.

trip counter returns to zero. To automatically bypass it, the zone must trip a full three
times within a subsequent hour.
A report of the swinger bypass is automatically sent to the receiver. Keypads on the
system display the zone name followed by – BYPAS until a Sensor Reset is performed or
the zone automatically resets when Reset Swinger Bypass is enabled.
7.10
RETARD: NO YES
Zone Retard
When you select YES
functions only in zone short conditions.
The zone must remain shorted for the full length of the Retard Delay before the panel
recognizes its condition. If you select NO, the zone operates without a Retard Delay.
7.11
CRS ZONE NO YES
Cross Zone
Select YES to enable cross zoning for this zone. Cross zoning requires this zone to trip
twice, or this zone and another cross zoned zone to trip prior to a Sensor Reset, before
an alarm report is sent to the receiver.
How it works

the zone activates and the Cross Zone Fault Time
to count down. If the same zone or another zone programmed for cross zoning trips
within this time, or prior to a Sensor Reset, an alarm report is sent to the receiver for
both zones.
If no other zone programmed for cross zoning trips before the cross zone fault time
expires, the panel sends a fault report for the zone to the receiver. This fault report
does not inhibit a second zone from tripping and generating an alarm prior to the next
Sensor Reset.
If the zone programmed for cross zoning trips and then restores and trips again, the
panel sends an alarm report for that zone only.
Cross zoning is not selectable on Fire Verify zone types.
7.12
ZONE NO: –
Zone Number

section and follow each programming prompt description. If all zones are
programmed, press the Back Arrow key at the ZONE NO: – display to continue.