Specifications
XR5 Programming Guide Digital Monitoring Products
15
zone inFormaTion
7.8
ARMED OPEN
Armed open
output to activate, and the Relay output action.
7.8.1
MSG: TROUBLE
Message to Transmit
You can send two report types to the receiver: Alarm and Trouble. These are
represented by the characters A and T. Press any top row Select key to display the
zone full reporting options.
A T L -
Alarm - Selecting A, allows an alarm report to be sent to the receiver and the bell
output to activate according to zone type. See the Bell Action section. The zone
name appears in the panel alarmed zones status list.
Trouble - Selecting T allows a trouble report to be sent to the receiver and the zone
name to appear in the panel alarmed zones status list.
You cannot change the Alarm (A) and Trouble (T) action for Fire (FI), Fire Verify
(FV), or Supervisory (SV) zone types.
Local - When you select L
output still activates according to zone type and the zone name appears in the panel
alarmed zones status list.
NOTE: You can also select L for a zone to send alarm reports to the subscriber's
personal pager only, and not to the central station. You must enable the Pager
option in the Communication section to operate this feature.
– (dash) - When you select –
7.8.2
OUTPUT NO: 0
Output Number
You can specify any of the outputs on the XR5FC or XR5SL to activate by a zone
condition. The output can be activated regardless of the report to transmit or
whether or not the zone is programmed as local.
7.8.3
ACTION:
Output Action
action to the relay. A description of the available output actions follows:
STD PLS MOM FOLW
Steady - The output is turned on and remains on until a Sensor Reset is performed or
the output cutoff time expires.
Pulse - The output alternates one second on and one second off until a Sensor Reset
is performed or the output cutoff time expires.
Momentary - The output is turned on only once for one second.
Follow - The output is turned on and remains on while the zone is in an off normal,
or bad condition. When the zone restores, the output is turned off.
the same three selections for Armed Short conditions. When you have programmed
all of the zone conditions, the Swinger Bypass selection then dis plays.