Specifications

Digital Monitoring Products XR5 Programming Guide
14
zone inFormaTion
7.5
NEXT ZN? NO YES
Next Zone?
When YES is selected, the programming for the zone terminates and the display
returns to ZONE NO: - allowing you to enter a new zone number. To make changes
to the Alarm Action for a zone, answer the NEXT ZONE? prompt with NO. The Alarm

7.6
ALARM ACTION . . . .
Alarm Action

characteristics of a zone type.
The Fire Verify zone type functions the same as Fire zone with the following
exceptions: When a Fire Verify zone is placed into shorted condition, the panel
performs a Sensor Reset and does not send a report. If any Fire Verify or Fire zone
initiates an alarm within 120 seconds after the reset, an alarm is indicated. If an
alarm is initiated after 120 seconds, the cycle repeats. If no other Fire Verify or Fire
zone is alarmed within 120 seconds, a zone fault report is sent to the receiver.
7.7 ZoneTypeSpecications

types provide the most commonly selected functions for their applications.
Zone Information Type Open Short
Swinger
Bypass
Retard
Delay
Cross
Zone
Use this section of the
programming sheet to record
the program options you
selected for the XR5 panel
zone.
FI
SV
A1
FV
Message
Output
Action
Message
Output
Action
A
T
L
0
to
4
S
P
M
F
A
T
L
0
to
4
S
P
M
F
N
or
Y
N
or
Y
N
or
Y
Fire FI T 0 A 0 N N N
Supervisory SV T 0 A 0 N N N
Auxiliary 1 A1 T 0 A 0 N N N
Fire Verify FV T 0 A 0 N N
No. Zone Name
1
2
3
4
5
31
32
33
34
Programmable Zone Options Descriptions
Below is a description of the various zone options shown on the table above.
Zone Information - The complete spellings of the abbreviations used for the zone types.
Type - The abbreviations that display on the keypad for the zone types.
Message - A T L 
Output - This only refers to the four XR5FC/XR5SL relay outputs.
Action 
Swinger Bypass - Allows the zone to be automatically bypassed after three trips.
Retard Delay - Provides a time delay before an alarm initiates from a short on this zone.
Cross Zone - Provides cross zoning for this zone.