Specifications
XR5 Programming Guide Digital Monitoring Products
13
zone inFormaTion
Zone Information
7.1
ZONE INFORMATION
Zone Information
A description of each programming option follows:
7.2
ZONE NO: –
Zone Number
Address Programming Zone Number
Panel 1-5
3 31-34
7.3
NAME: * UNUSED *
Zone Name
operating zone in the system must be given a name. This name can display at the
sent to the receiver as part of a zone event report.
A zone that is not part of the system must be marked *UNUSED*. To mark a zone
key. The pro grammer auto matically pro grams the name as * UNUSED *. If you
selected DEFAULTS? NO YES to clear the panel memory during Initialization, the
zones are already marked * UNUSED *.
7.4
ZONE TYPE: FIRE
Zone Type
When you assign a Zone Type to a zone, automatic responses are made for the zone.
To enter a new Zone Type, press any top row Select key. The display lists the
following four Zone Types.
F I SV A1 FV
FI SV A1 FV
Note: Supervisory Type zones provide default zone names: If SV (Supervisory) is
the 10-character zone name.
When the Zone Type you want to select displays, press the Select key beneath its
Action for each Zone Type.
Zone Type Descriptions
FI
stations, and beam detectors. Cross zoning is compatible with the Fire zone type.
SV (Supervisory zone) - Used to provide 24-hour zone supervision to devices
Indicator Valves (PIVs), gate valves, and low and high temperature gauges.
A1 (Auxiliary 1) - These zones allow you to customize the operation for peripheral
FV (Fire Verify zone) - Used primarily for smoke detector circuits to verify the
panel performs a Fire Reset. If any Fire zone initiates an alarm within 120 seconds
after the reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the
cycle repeats.