Specifications
Digital Monitoring Products XR5 Programming Guide
10
SySTem oPTionS
System Options
5.1
SYSTEM OPTIONS
System Options
This section allows you to select system wide parameters used in the operation of the
XR5FC and XR5SL system.
5.2
CRS ZONE TM: 0
Cross Zone Fault Time
a zone programmed for cross zoning trips, the panel begins counting down the Cross
Zone Fault Time you enter here. If the same zone or another zone trips within this
time, or prior to a Sensor Reset, an alarm report is sent to the receiver for both zones.
If the Cross Zone Fault Time expires without the second zone trip, a zone fault report
The Cross Zone Fault Time can be set from 4 to 250 seconds in one second increments.
5.3
RETARD DLY: 0
Zone Retard Delay
The Retard Delay can be set from 0 to 250 seconds in one-second increments.
5.4
PWR FAIL HRS: 1
Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off for
the length of the programmed delay time, an AC power failure report is sent to the
receiver.
The delay time can be set from 0 to 15 hours. Default is 1.
5.5
RST SBYP NO YES
Reset Swinger Bypass
When YES is selected, a swinger bypassed zone is automatically reset if it remains
in a normal condition for one hour after being bypassed. A report of the reset is
automatically sent to the receiver.