Installation guide
Page 3
Introduction
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR3F/XR5F Installation Guide
System Components
3.1 Description
A basic XR5 system is made up of the alarm panel with built in communicator, an enclosure, a 16.5 VAC wire-in
transformer, and a 12 VDC 7.0Ah battery. You can add up to two alphanumeric Security Command keypads and
one LED Security Command keypad to the panel and also connect control and annunciating devices to the
panel's Form C and annunciator outputs. Refer to section 6.6 in this guide when calculating power requirements.
3.2 XR5FC Wiring diagram
The XR5FC system below shows some of the accessory devices you can connect for use in various
applications.
Figure 1: XR5FC wiring diagram
Panel Reset
Zones 2 to 5 compatibility
identifier: A
Maximum operating range:
8.8 VDC to 14.2 VDC.
RED
BLACK
22 GA. MIN
GREEN
22 GA. MIN
BLACK
22 GA. MIN
YELLOW
22 GA. MIN
RED
Maximum AC wire distance
With 16 gauge wire: 70 feet
With 18 guage wire: 40 feet
Cold Water Pipe
Earth Ground
16 to 18 gauge wire
Output Header J11
Two Form C (SPDT) Outputs.
ZONE 2
AC
1
234
78
10 11 12
13
14
15
16
AC B+ B–
9
RED
YEL GRN
BLK
Z1B–
Z2 –
Z2+
3.3k Ω
Heat detectors, pull stations,
or any other contact devices
listed for Fire Protective
Signaling can be connected to
zones 1 to 5.
1
2
3
4
J12
Z1A–
Z1B+
Z1A+
MODEL XR5
MAIN
BACKUP
PANEL
RESET
J11
N/C COM N/O N/C COM N/O
Output Header J12
Four Open Collector Outputs.
Use Model 300 Harness.
50mA at 30 VDC resistive
Relay Sockets for Optional
Form C Outputs on J11
J4
J5
Telephone Connections
ZONE 1
J10 Trouble Annunciator Header
S
S
DMP transformer
Model 320
16.5 VAC 40VA
wire-in
Keypads
Models 690
100mA at 8 to 16 VDC.
Up to two alpha keypads
and one LED keypad can be
connected to the XR5FC.
Direct connect to unswitched
120 VAC 60 Hz
Secondary Power Supply
1.2 Amps max. charging current.
Use only 12 VDC rechargable
batteries. DMP Model 367.
Replace every 3 to 5 years.
All outputs must be
connected to devices
located within the same
room as the panel.
Up to 500mA auxiliary
current at 12 VDC from
Terminal 7.
See section 11.4 in the XR5FC
Installation Guide (LT-0299) for a list
of approved 2-wire smoke detectors.
16-Character Keypads
32-Character Keypads
10 Zone LED Keypads
5
6
BELL
SMK
ZONE 4
3.3k Ω
ZONE 5
3.3k Ω
Bell Circuit
1.5 Amps at 12 VDC
Minimum cutoff time 5
minutes
Aux. Power
Ground
Alarm Input
Bell Input
Bell Out Pos
Bell Out Neg
Bell Trouble
Bell Trouble
10k Ω
Model 308
Power
Supervision
Relay
Model 692F
40mA at 8 to 16 VDC.
Models 670
100mA at 8 to 16 VDC (125mA with display lit).
–
+
3.3k Ω
Smoke
Detector
–
+
Smoke
Detector
ZONE 3
For sprinkler
supervision, Normally
Open devices must be
used.
Red
Black
Model 866
Class B (Style W)
Notification Circuit Module
37mA at 12 VDC
All modules must be installed in
an approved enclosure within 20
feet and connected by conduit.
Refer to LT-0164 for a list of approved
4-wire smoke detectors and power
supervision relays.
Output 1
Output 2
OUTPUT 1
OUTPUT 2
SILENCE/RESET
PUSH FOR ONE SECOND
Silence/Reset
Button
Silence/Reset
Header
17
18
Z3 –
Z3+
19
20
Z4 –
Z4+
21
22
Z5 –
Z5+
W
W
S S
S
S
S
S S
S S
S SS S S S S S S
S
S
S
S S
= Supervised Circuit
S
377 Trouble Annunciator Module
Refer to the Model 377 Installation
Instructions (LT-0314).
Wiring on
terminals 5
through 22 must
exit to the right
and maintain a
1/4" separation
from the AC and
battery positive
wiring.
Up to 100mA of current is
available for 4-wire smoke
detectors from terminal 6.