Installation guide

Page 1
Introduction
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR3F/XR5F Installation Guide
Panel Specifications
1.1 Power supply
Primary Power Input: 16.5 VAC 40VA (Model 320 wire-in) or 12/24 VDC from Fire Alarm Control Panel (FACP)
Standby Batteries: One or two 12 VDC 7.0Ah
Auxiliary Output: 500mA at 12 VDC
Bell Output: 1.5 Amps at 12 VDC (XR5FC only)
Smoke Detector Output: 100mA at 12 VDC (XR5FC only)
All circuits inherent power limited except the red battery wire.
1.2 Communication
Built-in SDLC Digital Dialer communication to DMP Model SCS-1 Receivers.
Built-in 4-2 communication to non-DMP receivers.
Can operate as a local system (XR5FC only).
1.3 Panel zones
One Class A (Style D) zone (terminals 11 to 14).
Four 3.3K EOL Class B (Style A) powered fire zones with reset capability (terminals 15 to 22).
1.4 Remote Annunciators (Alphanumeric or LED Keypads)
You can connect alpha Security Command keypads and LED keypads to the XR5FC and XR5SL keypad data
bus. The panels do not support zone expansion on the bus.
1.5 Auxiliary Outputs
Two Form C (SPDT) outputs (Outputs 1 and 2). Each output requires one Model 305 plug-in relay. Each relay is
rated for 1 Amp at 30 VDC.
Four open collector annunciator outputs (Outputs 1 to 4). No relay is required. Each output is rated for 50mA at
30 VDC resistive.
1.6 Push button reset
The XR5FC and XR5SL panels each provide a push button mounted on the printed circuit board that allows
authorized users to reset latch detectors and silence active alarm bell ouputs. See section 16.1.
1.7 Enclosure specifications
The XR5 panels are shipped in an enclosure with end of line resistors, battery leads, user's guide, and
programming sheet.
XR5FC XR5SL
Size: 12.5" W x 9.5" H x 3.75" D Size: 12.5" W x 9.5" H x 2.75" D
Weight: 4 lbs Weight: 4 lbs
Color: Red Color: Red
Construction: 20 gauge cold rolled steel Construction: 20 gauge cold rolled steel
Introduction
2.1 Description
The DMP XR5FC and XR5SL Commercial Fire Panels are powerful 12 VDC fire alarm communicators with
battery backup that can also be powered from the12 or 24 VDC auxiliary output of a Fire Alarm Control Panel
(FACP). Each panel provides one Class A (Style D) fire zone and four Class B (Style A) powered fire zones with
reset capability for 2-wire smoke detectors, relays, or other latching devices.
The XR5 panels can communicate to one or two DMP SCS-1 Receivers using SDLC digital dialer or to one or
two non-DMP receivers using the 4-2 reporting format.