Installation guide
Page 14
Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR5FC/XR5SL Installation Guide
21.2 Multiple 865 Notification Circuit Modules
ZONE 2
AC
1
234
78
10 11 12
13
14
15
16
AC B+ B–
9
RED
YEL GRN
BLK
Z1B–
Z2 –
Z2+
3.3k Ω
U21
1
2
3
4
J12
Z1A–
Z1B+
Z1A+
MODEL XR5
MAIN
BACKUP
PANEL
RESET
EPROM Socket
J11
N/C COM N/O N/C COM N/O
J4
J5
Telephone Connections
ZONE 1
S
S
5
6
BELL
SMK
OUTPUT 1
OUTPUT 2
SILENCE/RESET
PUSH FOR ONE SECOND
17
18
Z3 –
Z3+
19
20
Z4 –
Z4+
21
22
Z5 –
Z5+
W
W
3.3k Ω
ZONE 4
3.3k Ω
ZONE 3
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power + Input
Bell Power – Input
Bell A + Output -
Bell A – Output
Bell B + Output
Bell Trouble
Bell Trouble
Bell B – Output
9
10
11
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power + Input
Bell Power – Input
Bell A + Output -
Bell A – Output
Bell B + Output
Bell Trouble
Bell Trouble
Bell B – Output
9
10
11
AUXILIARY
POWER
SUPPLY
24 VDC 5 Amp
Maximum
Power Supply
Trouble Contacts
N/C
UL Listed, Polarized
Indicating Devices.
Style Z
Notification Circuit Module
DMP Model 865
85mA at 12 VDC
The Auxiliary Power Supply and Indicating
Circuit Module trouble contact zone must
be programmed as a Supervisory Type zone.
NOTE: If an auxiliary supply is not used,
terminals 3 and 4 on the 865 Notification
Circuit Module can be jumpered together
to supply bell power from the XR5F panel.
A maximum of 1.5 Amps at 12 VDC is available
from terminal 5 of the XR5F.
Auxiliary power supply must be regulated
UL listed for Fire Protection Signaling Service.
Power supplies must have battery backup.
UL Listed, Polarized
Indicating Devices.
10k Ω EOL Resistor
DMP Model 308
AUXILIARY
POWER
SUPPLY
Power Supply
Trouble Contacts
N/C
24 VDC 5 Amp
Maximum
3.3k Ω
Each 865 Notification Circuit Module
in alarm draws up to 85mA from its
terminal 3 alarm input.
Notification Circuit Module
DMP Model 865
85mA at 12 VDC
Style Y
To additional three 865 Notification Circuit
Modules. Up to a maximum of five 865
modules on the XR5 panels. Modules must
be installed in a Model 340FC, 340SL, 349, or
350 enclosure connected by no more than 20
feet of conduit.
S
= Supervised Circuit
S
SS S S
S S S S S S S S
S
S
S
S
S