7.0 INSTALLATION
7.1 System Component Installation
A. When used in NFPA 72 compliant installations, the FACP shall be on an electrical circuit dedicated branch
in accordance with the National Electrical Code (NEC) and the local authority having jurisdiction (AHJ).
This circuit shall be available only to authorized personnel and shall be clearly labeled “FIRE ALARM
CIRCUIT CONTROL”.
B. Materials shall be installed in strict compliance with all local, state, county, province, district, federal
and other applicable building, safety, and fire standards, laws, codes, regulations, and guidelines
including, but not limited to, all appendices and amendments and the requirements of the local authority
having jurisdiction (AHJ).
7.2 Installers Responsibility
The installer shall be responsible for coordinating the installation of all fire alarm equipment. All work shall
be performed in accordance with the Digital Monitoring Products, Inc. instructions and in a manner
satisfactory to the owner’s representative. The installer shall be fully qualified in the installation,
operation, and programming of the system.
7.3 Lightning Suppression
The system shall include an optional lightning suppressor module that intercepts and directs lightning,
transient, and RF interference to ground.