Specifications

10 XR2500F Fire Detection Specification
5.0 FUNCTIONAL DESCRIPTIONS
5.1 System Description
A. The system areas and zones shall be programmable, and the system shall store, log, display, and transmit
specific custom designations for system areas, zones, and user names.
B. To ensure continued, one-call support, the system shall be constructed of sensing components provided
directly by the system manufacturer, such as power supplies, smoke and heat detectors, manual fire
alarm stations, or other sensing devices that the manufacturer offers.
C. The system controller, user interfaces, zone input devices, relay output devices, and the system signal
receiving equipment shall be engineered, manufactured, assembled, and must be distributed from a
location within the United States of America.
D. The system shall support user interaction by way of a Remote Annunciator, system software, or key
switch, using integrated or auxiliary devices provided by the system manufacturer.
E. The system shall support controller zone input connections, system Remote Annunciators, and system
zone expansion modules up to 562 fire input zones.
F. The system shall be capable of offering at least five (5) zone expansion buses, each of which can support
the connection of up to 15,000 feet of four-wire cable. Zone expansion and keypad data buses that
exceed 2,500 feet of cable must include splitter/repeater modules to boost data voltage and maintain
data integrity.
G. The system shall provide a seamless capability to provide a minimum of 500 addressable relays, which
can be located at any connection location upon a zone expansion bus.
H. System relay outputs shall have the capability of being triggered as a result of a command from the user
interface, changes in system status, changes in zone status, or by a programmable schedule.
I. System relay output states shall be programmable for momentary, maintained, pulsed, or must follow the
state of an associated system zone input.
J. The system shall be completely programmable either locally from a Remote Annunciator or remotely
through a standard dial-up, and network connections by way of a LAN, WAN, and/or by way of the
Internet.
K. The control unit shall be completely programmable remotely using Remote Annunciators, and/or using
upload/download software that communicates using SDLC 300 baud, 2400 baud, or IP Addressed data
network. On-site programming from a personal computer shall also be permitted.
L. The control unit shall be equipped with an anti-reversing circuit breaker to prevent damage due to
accidental reversal of battery leads.
5.2 Output Capacity
A. This system shall be capable of monitoring a maximum of 562 individual zones and controlling a maximum
of 502 output relays.
B. The FACP shall have, as an integral part of the assembly, two (2) SPDT Form C relays rated at 1 Amp at
30 VDC and four (4) open collector 12 VDC outputs rated at 50mA each. It shall also have the capacity of
a maximum of 125 output expander modules with 500 switched ground, open collector outputs, 50mA
maximum and 500 auxiliary relays (Form C rated at 1.0 Amp at 30 VDC).
C. The panel shall also provide 100 programmable output schedules, and include an integral bell alarm
circuit providing at least 1.5 Amps of steady, pulsed, or temporal bell output. Output type shall be
programmable by zone type. Relays and voltage outputs shall be capable of being independently
programmed to turn on and/or off at selected times each day.