23.6 Cross Zoning
Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to
allow an intruder to trip both devices before it expires. A Cross Zone Time that is too short may allow an
intruder to trip the devices and allow only a zone fault report be sent to the central station.
WhenaCrossZonedzonetripsaFAULTreportissenttotheSCS-1RReceiver.WhentwoCrossZonedzones
tripwithintheCrossZoneTime,bothzonessendALARMsignalstothereceiver.Forexample,ifzones1
and2areCrossZonedzones,andonlyzone1trips,aFAULTreportissenttothereceiverforzone1.If
zone1tripsandzone2tripswithintheCrossZoneTime,anALARMreportissenttothereceiverforzone
1 and zone 2.
23.7 Events Manager
The Events Manager allows you to delay sending
certain reports to the central station receiver.
Reports can be kept in the panel memory until
overwritten by new activity or held until the
memory buffer reaches 50 events or 50 door access
grantedevents.Whenthebufferisfull,thepanel
automatically sends the stored reports to the
central station receiver. The table lists the panel
reports you can delay using the Events Manager
option.
23.8 UserProles
Aproledenestheauthorityofeachuser
codeinthesystem.Prolesareprogrammedin
theKeypadUserMenu.Severalcharacteristics
associatedwitheachUserProledeneits
authority within the system. To effectively
programanXR500Seriessystem,youmustunderstandtheinterrelationshipbetweenproles,devices,
outputgroups,andareas.BelowisabriefexplanationoftheUserProleelements.Formoreinformation
aboutuserproles,refertotheUserProlesRecordandtheXR100/XR500User’sGuide(LT-0683).
Note:ProlescannotbechangedviakeypadinanAll/PerimeterorHome/Sleep/Awaysystem.Usethe
defaultproles1through10.
Prole Number-Eachprolemaybeassignedauniquenumberfrom1to99.
Prole Name-Eachprolemaybeassigneda32-charactername.TheProleNumberisthedefaultname.
Area Number -Eachprolemaybeassignedspecicareasofthesystemforarminganddisarming.
Whencreatingproles1to98,NOareasareassignedbydefault.Thedefaultforprole99isALLareas
assigned.Prole99ispreprogrammedinthesystematthefactory.
Access Area Number-Eachprolemaybeassigneddooraccessareaassignments.Defaultforprole1to98
isNOareasassigned.Defaultforprole99isALLareasassigned.Prole99ispreprogrammedatthefactory.
Output Group Assignment-Eachprolemaybeassignedanoutputgroupnumberfrom1to10.Default
forprole1to98isNOoutputgroupassigned.Defaultforprole99isoutputgroup10. Your system may
by programmed to turn on an output group at certain keypads when door access occurs.
User Menu Assignments-Eachuserprolemayhaveanyofthemenusassignedtoitasshowninthe
followingUserProleRecord.TheUserProleRecordliststheusermenuproleassignmentsandthe
systemfunctionsusersareallowedtoaccessbasedontheprolenumbersassignedtotheircodes.
Alwaysmakesurethatatleastoneadministratorinyoursystemhasaprolewithall authorities and
areas.
Report Type Immediately Delayed
Alarm Y
Trouble Y
Restore Y
Opening Y
Closing Y
Bypass Y
Reset Y
Supervisory Y
Add Codes Y
Delete Codes Y
Change Codes Y
Permanent Schedule Change Y
Temporary Schedule Change Y
Door Access Y
Door Access Denied Y
Late to Close Y
Force Armed Zone Y