23.4 Using the Walk Test
The XR500 Series panel provides a walk test feature that allows a single technician to test the protection
devicesconnectedtozonesonthesystem.ConducttheWalkTestwithin30minutesofresettingthe
panel.TheWalkTestautomaticallyendsifnozonesaretrippedfor20minutes.TESTINPROGRESS
displaysatallkeypadsprogrammedwiththesameAreaDisplayfeatures.Whenveminutesremain,TEST
ENDWARNINGdisplays.TheWalkTestonlytestszonesassignedtotheareasprogrammedintothekeypad
inAreaDisplay.IfanyareasarearmedtheWalkTestdoesnotstartandSYSTEMARMEDdisplays.
WALK TEST
Walk Test
ToconducttheWalkTest,resetthecontrolpanelbymomentarilyplacingajumper
onJ16.Fromthekeypad,enterthecode8144.ThekeypaddisplaysWALKTEST
for four seconds. If the system is monitored and the communication type is DD or
NET, the system sends a System Test Begin report to the central station. After four
seconds, the keypad displays the zone type choices for testing.
Note: If ENHANCED ZONE TESTinSystemOptionsissettoYES,theWalkTestcan
belimitedtoonlyoperateduringtheArea32,Shift4scheduleifprogrammed.Ifno
schedule is entered, the walk test always operates.
BG FI PN SV
Zone Types
Select the zone type you want to test. An asterisk next to the zone type indicates
the zone type chosen for testing. Press the Select key again to deselect the zone
type.Whenyouhaveselectedallthezonetypesyouwantfortesting,pressthe
COMMANDkeytodisplaythenextWalkTestoption.PressingtheBackArrowkey
exitstheWalkTest.
Note:FortheWirelessCheck-inTest,makesurenozonetypesareselectedand
presstheCOMMANDkey.PressingtheBackArrowkeyexitstheWalkTest.
BG(Burglaryzones)-SelectBG to test burglary zones. Includes all NT, DY, EX, A1,
and A2 zones.
FI(Firezones)-SelectFItotestrezones.IncludesallFIandFVzones.
PN(Paniczones)-SelectPN to test panic zones. Includes all PN and EM zones.
SV(Supervisoryzones)-SelectSV to test supervisory zones. Includes all SV zones.
Note: DuringtheWalkTest,tripeachzonedeviceorbuttononthesystemfor1to2
seconds. You do NOT have to hold the zones for 2 seconds in normal mode for PN
typezones.YouareonlyrequiredtoholdthepanicduringtheWalkTestbecause
the zone takes additional time to report when the system is in test mode.
WLS PIR
WLS(WirelessCheck-inTest)-SelectWLStoautomaticallytestwirelesstransmitter
communications. Includes all wireless devices except key fobs and transmitters
programmedforasupervisiontimeof0(zero).
PIR(WirelessPIRWalkTest)-ThePIRWalkTestallowstheinstallertoverifythe1126
operation.Whenenabled,the1126LEDasheseachtimemotionisdetectedforupto
30minutes.ThisisalocaltestonlyandnomessagesaresenttotheCentralStation.
BELL NO YES PULS
Bell Action
This option selects the bell output action when a zone under test faults. This option
allowsthepanelbell,and/orburglarybell,and/orrebelltoturnONandthenOFF
eachtimeazoneistripped(openedorshorted).
NO -SelectNOfornobelloutputactionduringWalkTest.
YES - SelectYEStoturnonanybelloutputfor2secondsduringWalkTest.
PULS -SelectPULStoturnonanybelloutputfor1/4secondduringWalkTest.Any
LX-Busdeviceoutputturnsonfor1.6secondsduetothepollingcycle.
TRIPS: XXX END
Trip Counter For Walk Test
OnceintheWalkTest,walkaroundandtripeachprotectivedevice.Continue
tripping devices until the entire system is tested.
WitheachzonetripduringtheWalkTest:
• Keypaddisplayincrementseachtimeaselectedzoneisopenedorshorted
• Thekeypadbuzzesfortwoseconds
• ThepanelsoundsthealarmbellsasprogrammedinBellAction
• EachtimeaFI,FV,orSVzonetrips,aSensorResetoccurs.