Programming instructions
XR500 Series Programming Guide Digital Monitoring Products
55
zone informaTion
19.22
PRESGNL KEYPADS:
Presignal Keypad Addresses
You can enable any combina tion of keypad addresses to sound a presignal tone
during the time a zone is in retard delay. The presignal tone si lences when the zone
restores or the re tard delay expires.
To en able a presignal ad dress, press any top row Select key followed by the number
of the keypad address. You can enable the presignal for all 16 keypad addresses.
To disable a presignal address press the matching number digit again. Press the
COMMANDkeywhentheaddressselectioniscomplete.ThePresignalpromptisonly
displayed when Retard is selected as YES.
19.23
FAST RSP NO YES
Fast Response
SelectYEStoprovideazoneresponsetimeof167ms.SelectNOtoprovideanormal
zoneresponsetimeof500ms.Zones500to999haveaxedresponsetimeanddo
not display this prompt.
19.24
CRS ZONE NO YES
Cross Zone
Select YES to enable cross zoning for this zone. Cross zoning requires one or more armed
zones to fault within a programmed time before an alarm report is sent to the receiver.
Whentherstcrosszonedzonetrips,thecrosszonetimespeciedinSystem
Optionsbeginstocountdown.Whenasecondcrosszonedzonetripsortherst
zone trips a second time before the end of the count down, the bell action assigned
to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel
sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning
for Fire verify zones or for any Fire zones that have Retard Delay enabled.
Note: For UL Installations, Cross Zoned zones must protect the same area.
19.25
PRIORITY NO YES
Priority
Select YES to provide additional protection for the premises by requiring this zone to
be in a normal condition before its assigned area can be armed.
19.26 Fire Panel Slave Input
ThisoptionisavailableonFireZones(FI)onlyandallowsarezonetheabilityto
provideslavecommunicationoperationforaseparaterealarmcontrolpanel.If
YES,thiszonewilltransmitarestoralimmediatelywhenrestoredbytherepanel
being monitored. A sensor reset is not required to generate the restoral message.
IfNO,thiszonewilloperateasastandardretypezoneandasensorresetis
requiredbeforethezonewillreturntonormal.DefaultisNO.
19.27 Area Follower
Allows Night, Day, Aux 1, or Aux 2 burglary zones to be delayed by following any exit
orentrydelaythatiscurrentlyrunningintheareathatisspecied.Defaultis0.
19.28 Zone Real-Time Status
SelectingYESallowsReal-TimeStatusreports,suchasDoorOpenorClosedwith
zonenumber,tobesentusingPCLogreporting.SelectingNOdisablesReal-Time
Statusforthiszone.DefaultisNO.
19.28.1 Door Number
IfZONEREAL-TIMESTATUSisselectedasYES,enteradoornumber(keypadbus
address)of1-16.Whenadoornumberisselected,thedoornumberisincluded
inthestatusreportinsteadofthezonenumber.Enter0(zero)todisablethis
featureandreportthezonenumber.Defaultis0(nodoor).
19.29
ZONE AUDIT DAYS:
Zone Audit Days
Enterthenumberofdays(0to365)allowedtoelapsewithoutthezonebeingtripped
beforeafaultmessageissent.Themessageissenttothereceiver(s)programmed
toreceiveSupervisory/TroubleReportsat10:00amfollowingtheexpirationofthe
timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins
to countdown the number of days programmed. After the countdown expires, a fault
message is sent and the Zone Audit Days timer restarts and begins to countdown the
numberofdaysprogrammed.Availableforallzonetypesexceptreandreverify.
Enter0(zero)todisablethisfunction.Defaultis0(zero).
FOLLOW AREA: 0
ZONE REAL-TIME
STATUS
NO YES
FIRE PANEL SLAVE
INPUT: NO YES
DOOR NUMBER: 0
0