Programming instructions

Digital Monitoring Products XR500 Series Programming Guide
54
zone informaTion
19.17
OUTPUT: NONE
Output Action
EnteringanOutputNumberdisplaysthisprompt.Thispromptallowsyoutoassign
an output action to the relay: Steady, Pulse, Momentary, or Follow.
Note: Some wireless devices whether powered using an AC adaptor or a battery,
ignore some output action programming.
STD PLS MOM FOLW
STEADY - The output is turned on and remains on until the area is disarmed, an
output cutoff time expires, or the output is reset from the keypad menu.
PULSE - The output alternates one second on and one second off.
Note:ThepulsingrateforaModel716relayattachedtotheLX-Busis1.6seconds.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an off normal,
orbadcondition.Whenthezonerestores,theoutputisturnedoff.
After you make the three selections in the sections above, the display prompts you for the same three
selectionsforDisarmedShort,ArmedOpen,andArmedShortconditions.Ifthezoneisa24-hourtype,
onlytheArmedOpenandArmedShortconditionsdisplay.Whenyouhaveprogrammedallofthezone
conditions, the Swinger Bypass selection then dis plays.
19.18
SWGR BYP NO YES
Swinger Bypass
Selecting YES allows the zone to be swinger bypassed by the panel according to the
specications programmed in Swinger BypassTrips and Reset Swinger Bypass. The
Bypass condition displays in the keypad Status List. Selecting NOdisables swinger
bypassing for this zone.
How it works
Ifwithinonehour,azonetripsthetotalnumberoftimesasspeciedinSwinger
Bypass Trips, the panel bypasses it until the following conditions occur; the area
in which the zone is assigned is disarmed, the zone is manually reset through the
Bypass Zones? keypad User Menu function, the zone remains normal for one hour and
the Reset Swinger Bypass is YES.
Ifthezonetripsfewerthanthespeciedtimeswithinonehour,thebypasstrip
counterreturnsto0(zero)andtheprocessmustberepeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES.
Note: Not investigated by UL.
19.19
PREWARN KEYPADS:
Prewarn Keypad Addresses
Attheentrydelaystart,allkeypadaddressesselectedheredisplayENTERCODE:-.
If you want the prewarn to sound at all 16 addresses, leave the default setting.
To delete an address, press the matching number on the keypad. To disable
prewarning at all keypads, press a top row Select key to clear the addresses shown.
PresstheCOMMANDkeywhentheaddressselectioniscomplete.
Theprewarntonestopsatthekeypadwheretherstusercodedigitisentered.If
nokeysarepressedforvesecondsoraninvalidusercodeisentered,theprewarn
tone resumes at that keypad.
19.20
ENTRY DELAY: 1
Entry Delay
Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System
Options.
19.21
RETARD NO YES
Zone Retard Delay
WhenyouselectYES,thezoneoperateswiththezoneretarddelay.Theretard
func tions only in zone short condi tions.
The zone must re main shorted for the full length of the re tard de lay before the
panelrecognizesitscondition.IfyouselectNO,thezoneoperateswithoutaretard
delay.
Note: For UL installations, Zone Retard Delay shall not be used for burglary
zones.