Programming instructions
XR500 Series Programming Guide Digital Monitoring Products
53
zone informaTion
19.15
MSG: TROUBLE
Report to Transmit
PressanySelectkeytodisplaythefollowingreportoptions:A,T,L,S,C,and-
(dash).
A T L -
ALARM - Select A to send an alarm report to the receiver and activate the bell
output according to zone type. The zone name appears in the panel alarmed zones
and status lists.
TROUBLE - Select T to send a trouble report to the receiver. The zone name
appears in the panel alarmed zones and status lists.
Note: ULrequirementspreventtheAlarm(A)andTrouble(T)actionforFire(FI),and
FireVerify(FV)zonetypesfrombeingchanged.
LOCAL - WhenyouselectL,analarmreportisNOTsenttothereceiver.Thebell
output activates and the zone name appears in the panel alarmed zones and status
lists.
- (Dash) - Whenyouselecta–(dash),reportsareNOTsenttothereceiver.Thebell
output does not activate and there is no display in the panel alarmed zones or status
list.Onlytherelayoutputselectedinthenextsectionoperates.
D S C
DOOR PROPPED-SelectingD allows the following operation: The time programmed
intoENTRYDLY4intheSystem Option section begins to count without displaying
on keypad. If the time expires and the zone has not returned to normal, the keypad
troublebuzzerstartsandCLOSETHEDOORappearsonthekeypadsprogrammedinto
thePREWARNADDRESSsection.ThetimeprogrammedintoENTRYDLY4beginsto
count down again internally. If the time expires a second time and the zone has not
returnedtonormal,afaultreportissenttothereceiverandthezonename-OPEN
message displays on the keypads until a code is entered. The bell output does not
activate for the Door Propped operation.
SILENCE/RESET - SelectSwhenthezone(notFI,SV,orFV)isconnectedtoaDMP
Model303Silence/Resetswitch,thezonecanbeusedtosilencethealarmbelland
performasensorresetwithoutusingakeypad.AreportisNOTsenttothereceiver
except for the bell silence report.
CANCEL AMBUSH - Select C for the zone to cancel the Early Morning Ambush timer
and stop an Ambush message from being sent to the receiver. Faulting the zone
takes the place of a second user code being entered at the keypad and is only
availablefornon-retypezones.Areaassignmentforthezonedoesnotaffectthis
option. See Early Morning Ambush in Area Information programming .
19.16
OUTPUT NO: 0
Output Number
YoucanspecifyanyoftheRelayOutputsontheXR500Seriespaneltobeactivated
byazonecondition(1to6,500to999ifModel716used,D1toD16,G1toG20).
The output can be activated regardless of the report to transmit or whether or not
the zone is programmed as local. An output activated by an armed zone is turned
off when the zone area is disarmed by a user.
To enter an output number, press a top row Select key followed by the output
number.PresstheCOMMANDkey.