Programming instructions

Digital Monitoring Products XR500 Series Programming Guide
52
zone informaTion
FA Series Wireless
For an FA Series Remote Wireless Receiver set the House Code to 99. See House Code programming in
SystemOptions.Onlyzones500to699canbeprogrammedasFASeriesWirelesszonesformaximumof
200WirelessZones.
For a DMP 1100X Wireless Receiver see section 16.10.
19.12
ZONE INFORMATION
WIRELESS? NO YES
Wireless
SelectYEStoprogramawirelesszoneconnectedtoanFASeriesFA400-DMPRemote
WirelessReceiver.PresstheCOMMANDkeytocontinuewithwirelessprogramming.
19.12.1
CHECK IN TM: 60
Check-in Time
Youcansetwirelesstransmitterstocheckinautomaticallyevery10,30,or60
seconds or not at all. To change the 60 second default, press any top row Select
keytodisplayNONE103060.Selectthecheck-intimeyouwantforthiszone.
Note:RefertotheWirelessCheck-inandSupervisionTimeDenitionssectionof
the Appendix for supervision information.
19.12.2
INT CONT NO YES
Internal Contact
SelectYEStouseaninternalcontactonthewirelesstransmitter.SelectNO
touseanexternalcontact.WhenyouselectNO,thefollowingtwoprompts
display.
19.12.3
EOL NO YES
End-of-Line
Select YES to supervise an external contact connected to the wireless
transmitter.Atthecontact,installa2.2kOhmEnd-of-Lineresistorinparallel
forNormallyOpencontactsandinseriesforNormallyClosedcontacts.
19.12.4
NRM OPEN NO YES
Normally Open
SelectNOifthecontactconnectedtothewirelesstransmitterisNormally
Closed.
19.12.5
NEXT ZONE NO YES
Next Zone
SelectYEStoreturntotheZONENO:-prompttoprogramanewzone.Select
NOtodisplaytheAlarmActionoption.
19.13
ALARM ACTION . . . .
Alarm Action
ThisoptionallowsyoutochangeanyZoneTypestandarddenitions.WhentheZone
Typeisspecied,theAlarmActionforthatzoneisstoredinmemory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a
non-24-hourzoneandtheAlarmActionprogramingbeginswithDisarmedOpen.
IftheZoneTypeisFire,Panic,Emergency,orSupervisoryitisa24-hourzonethatis
alwaysarmedandtheAlarmActionprogrammingbeginswithArmedOpen.
The Fire Verify Zone Type functions the same as Fire Type, with the following
exceptions:WhenaFireVerifyzoneinitiatesanalarm,thepanelperformsaSensor
Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the
reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is
repeated and a zone fault report is sent to the receiver.
DoNOTprogramFireVerifyZoneTypesforZoneRetard.
19.14
DISARMED OPEN
Disarmed Open
Denestheactiontakenbythepanelwhenthezoneisopenedwhiletheareais
disarmed.Therearethreeactionstodene:Reporttotransmit,RelayOutputto
activate,andRelayOutputaction.
YoumustalsomaketheseselectionsfortheDisarmedShort,ArmedOpen,andArmed
Shortzoneconditions.PressCOMMANDtocontinue.