Programming instructions

XR500 Series Programming Guide Digital Monitoring Products
45
zone informaTion
19.4
ZONE TYPE: BLANK
Zone Type
TheZoneTypedenesthepanelresponsetothezonebeingopenedorshorted.
ThisiscalledtheAlarmAction.Thereareupto13possiblealarmactionresponses
depending on the zone type and any restrictions it may have. See the Zone Type
chart in the Appendix.
WhenyouassignaZoneTypetoazone,automaticzoneresponsesaremade.There
are 12 Zone Types to choose from. Application descriptions for each zone type can
be found in the Appendix of this manual.
To enter a new Zone Type, press any Select key. The display lists all of the available
Zone Types four at a time.
- - NT DY EX
Blank,Night,Day,orExit.PressCOMMANDforadditionalzonetypes.
FI PN EM SV
Fire,Panic,Emergency,orSupervisory.PressCOMMANDforadditionalzonetypes.
A1 A2 FV AR
Auxiliary1,Auxiliary2,FireVerify,orArming(keyswitch).PressCOMMANDfor
additional zone types.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the Zone
Type, the zone must be assigned to an active area. If you select Fire, Fire Verify,
Panic,Emergency,orSupervisoryastheZoneType,itisa24-hourzonethatisalways
armed and no area assignment is needed.
Zone Type Specications
Thepanelcontains12defaultzonetypesforuseinconguringthesystem.Thesezone
types provide the most commonly selected functions for their applications. All zone
types except the Arming zone type can be customized by changing the options listed
below. Arming zone type programming continues at Arming Zone Area Assignment.
Refer to the Appendix for complete zone type descriptions.
19.5
AREA NO: -
Area Assignment
Enter the area number where the Night, Day, Exit, Auxiliary 1, or Auxiliary 2 zone
isbeingassigned.ForanAreasystem,areanumbers1-32canbeassigned.Fora
Home/Sleep/AwaywithGuestsystem,areanumbers1-9canbeassigned.
AREA: PERIMETER
InanAll/PerimeterorHome/Sleep/Awaysystem,thecurrentlyselectedarea,
Perimeter, Interior, Bedroom displays.
INT PERIM
OnanAll/Perimetersystem,selectINTtoprogramzonesfortheinteriorareaand
select PERIM to program zones for the perimeter area.
INT BDRM PERIM
OnaHome/Sleep/Awaysystem,selectINTtoprogramzonesfortheinteriorarea,
select BDRM to program zones for the bedroom area, and select PERIM to program
zones for the perimeter area.
19.6
FIRE BELL OUT: 0
Fire Bell Output
Thisoutput(1to6,500to999,G1toG20,orD1toD16)isturnedonanytimea
Fire, Fire Verify, or Supervisory zone is placed in alarm. The output is turned off by
any the following actions:
• WhentheUserMenuAlarmSilencefunctionisperformed.
• Whenavalidusercodeisenteredtosilencethebell.
• WhentheSilencekeyispressedonthe630FRemoteFireCommandCenter.
• UsingtheOutputsOn/OfffunctionintheUserMenu.
• TheexpirationoftheBellCutofftime.
Thisoutputcanbeconnectedtoalamp,LED,orbuzzerusingtheDMPModel716
OutputExpansionModule.