Programming instructions

Digital Monitoring Products XR500 Series Programming Guide
24
SySTem oPTionS
Note: For UL Installations, the combined Transmit Delay (Abort Window) and
Entry Delay must not exceed one (1) minute.
9.6
CRS ZONE TM: 4
Cross Zone Time
Enterthetimeallowedbetweenzonefaults.Whenzonesarecrosszoned,thesame
zone or a second cross zoned zone must fault within this time in order for an alarm
report for both zones to be sent to the receiver. If the cross zone time expires
withoutthesecondzonefaulting,onlyazonefaultfromtherstzoneisreported.
Cross-zonetimecanbefrom4to250seconds.Entering0(zero)disablesthis
function. Default is 4. See the Appendix.
9.7
RETARD DELAY: 10
Zone Retard Delay
Enter the retard time assigned to Fire, Supervisory, Auxiliary 1, Auxiliary 2, Arming,
and Panic type zones. The retard delay only functions when the zone is shorted.
The zone must remain shorted for the entire length of the Retard Delay before being
recognized by the panel. The Zone Retard Delay can be from 1 to 250 seconds.
Enteringa0(zero)disablesthisfunction.
9.8
PWR FAIL HRS: 1
Power Fail Delay
ThisoptiontracksthedurationofanACpowerfailure.WhentheACpowerisofffor
the length of the programmed delay time, an AC power failure report is sent to the
receiver.Thedelaytimecanbefrom1to15hours.Enteringa0(zero)sendsthe
powerfailurereportaftera15-seconddelay.Thedefaultsettingis1.
Note: For UL burglary installations Power Fail Delay shall be programmed to 0
(zero).
Note: For UL re installations, Power Fail Delay shall be programmed as required
by the service of the panel. For Central Station service: 6-12, for Remote Station
service: 12-15.
9.9
SWGRBYPS TRIPS: 1
Swinger Bypass Trips
Enterthenumberoftimes(1or2)azonecangointoanalarmortroublecondition
within one hour be fore being auto matically bypassed. You can select one or two
trips. Bypassed zones are auto matically reset when the area they are assigned to is
disarmed.All24-hourzonesareresetwhenanyareaofthesystemisdisarmed.A
programmingStopoperationrestoresabypassedzone.Entering0(zero)disables
this function. Default is 1.
How it works
The panel hour timer starts at 59 minutes past the hour. If the hour timer expires
beforethetripcounterisexceeded,thetripcounterreturnsto0(zero).Ifthetrip
counter is exceeded before the hour expires, the zone is auto matically bypassed by
the panel. A Bypass Re port is sent to the receiver if Bypass Re ports is YES.
Note: Not investigated by UL.
9.10
RST SBYP NO YES
Reset Swinger Bypass
WhenYESisselected,anautomaticallybypassedzoneisresetifitremainsina
normal condition for one complete hour after being bypassed. A report of the
automatic reset is sent to the receiver if Bypass Reports has been se lected as YES.
DefaultisNO.
Note: Not investigated by UL.
9.11
TIME CHG NO YES
Time Zone Changes
This function allows the panel to request automatic time changes from the DMP
SCS-1RReceiveronPath1.Forthereceivertosendtimechanges,itmustbe
programmed to send time changes and must be receiving time change updates from
the network automation computer at least every 24 hours. Default is YES.
HRS FROM GMT: 6
WhentimezoneisprogrammedYES,enterthenumber(0-23)thatindicatesthe
GreenwichTimezone(GMT)wherethepanelislocated.Thedefaultis6.