Programming instructions
XR500 Series Programming Guide Digital Monitoring Products
11
CommuniCaTion
3.22
RETRY SECONDS: 6
Retry Seconds
ThisoptiondisplaysforNETor232CommunicationTypes.
Enterthenumberofseconds(between6and15)thepanelshouldwaitbefore
retrying to send a message to the receiver if an acknowledgment was not received.
The panel retries as many times as possible for a period of one minute before
sending a network trouble message. For example, if retry time is set to 15, the
panel retries four times. The default Retry Time is 6 seconds.
Note: If TCP is enabled, the minimum Retry Time programmed is 6 seconds.
3.23
SUB CODE NO
Substitution Code
ThisoptiondisplayswhentheCommunicationTypeisNET,CELLor232.ThePanel
Substitution Code increases the level of security by helping to ensure that the panel
sending the message to the receiver has not been substituted by another panel. The
defaultisNO.
Select YES to send a substitution code with every message.
SelectSHARED(SHR)tousethesamesubstitutioncodeasoperatingintheprevious
path.
3.24
232 COMM PORT: O
232 Communication Port
ThisoptiondisplayswhenCommunicationTypeis232.
ThisoptionsetsthephysicalRS-232porttotheon-boardconnectororoneoftheDMP
Model 461 Interface Adaptor Card slots labeled A, B, C, D, or E. Use slot A if using a
462N Network Interface Card with or without the 461 card.
EnterOtousetheon-boardconnector.SettheXR500SeriespanelJ23jumperto
RandbrieyresetthepanelusingtheJ16jumpertoactivateRS-232operation.
DefaultisO(On-board).
3.25
-
-
232 SETUP:
232 Setup String
ThisoptiondisplayswhentheCommunicationTypeis232.Enter up to two lines of 16
characterstoequalupto32charactersforthedestinationaddressthatmayinclude
an IP address.Example:IfusingaDMPiCOM,enterAT#UCXXX.XXX.XXX.XXX#PPPPP
where X is the IP address and P is the port number.
3.26
893A: NO YES
893A
This option displays when the Communication Type is DD or CID.
The893AoptionallowsreportstobesenttothereceiveronasecondDDlineusing
the893Amodule.DefaultisNo.
Whenusingthisoption,TestReportmessages(S07AutomaticRecallTestor
S88UnrestoredSystemRecallTest)aresenttothereceiveratthefrequency
programmedinTestFrequency,alternatingbetweentherstandsecondphoneline.
Forexample,aDDpathwithan893Amodulesetfordailytestreportfrequency
sends a test report through phone line 1 one day and phone line 2 the next day.
Ifthe893AoptionissettoYES,enteruptoa3-digitprextobedialedbeforethe
secondphonenumber.Ifnoprexisentered,thesecondphonenumberisdialedas
originally entered.
3.27
ALARM SWITCH: 1
Alarm Switch
This prompt displays for DD or CID Communication Types.
Enter the number of attempts to send an alarm message before switching to the next
path.Rangeisfrom1to10.Allnon-alarmmessagesaresentfor10attemptsonthe
dialer before a switch is initiated. If the path immediately following this channel is
not a backup path, this option has no effect. Default is 1.
3.28
DUPLICATE ALARMS
Duplicate Alarms
ThispromptdisplaysforBACKUPpaths.IfYesisselected,thecurrentbackuppath
duplicates all alarms occurring on its group primary path. Default is No.
D E
O A B C
NO YES SHARED
NO YES
-
2ND LINE PREFIX: