Programming instructions

XR500 Series Programming Guide Digital Monitoring Products
11
CommuniCaTion
3.22
RETRY SECONDS: 6
Retry Seconds
ThisoptiondisplaysforNETor232CommunicationTypes.
Enterthenumberofseconds(between6and15)thepanelshouldwaitbefore
retrying to send a message to the receiver if an acknowledgment was not received.
The panel retries as many times as possible for a period of one minute before
sending a network trouble message. For example, if retry time is set to 15, the
panel retries four times. The default Retry Time is 6 seconds.
Note: If TCP is enabled, the minimum Retry Time programmed is 6 seconds.
3.23
SUB CODE NO
Substitution Code
ThisoptiondisplayswhentheCommunicationTypeisNET,CELLor232.ThePanel
Substitution Code increases the level of security by helping to ensure that the panel
sending the message to the receiver has not been substituted by another panel. The
defaultisNO.
Select YES to send a substitution code with every message.
SelectSHARED(SHR)tousethesamesubstitutioncodeasoperatingintheprevious
path.
3.24
232 COMM PORT: O
232 Communication Port
ThisoptiondisplayswhenCommunicationTypeis232.
ThisoptionsetsthephysicalRS-232porttotheon-boardconnectororoneoftheDMP
Model 461 Interface Adaptor Card slots labeled A, B, C, D, or E. Use slot A if using a
462N Network Interface Card with or without the 461 card.
EnterOtousetheon-boardconnector.SettheXR500SeriespanelJ23jumperto
RandbrieyresetthepanelusingtheJ16jumpertoactivateRS-232operation.
DefaultisO(On-board).
3.25
-
-
232 SETUP:
232 Setup String
ThisoptiondisplayswhentheCommunicationTypeis232.Enter up to two lines of 16
characterstoequalupto32charactersforthedestinationaddressthatmayinclude
an IP address.Example:IfusingaDMPiCOM,enterAT#UCXXX.XXX.XXX.XXX#PPPPP
where X is the IP address and P is the port number.
3.26
893A: NO YES
893A
This option displays when the Communication Type is DD or CID.
The893AoptionallowsreportstobesenttothereceiveronasecondDDlineusing
the893Amodule.DefaultisNo.
Whenusingthisoption,TestReportmessages(S07AutomaticRecallTestor
S88UnrestoredSystemRecallTest)aresenttothereceiveratthefrequency
programmedinTestFrequency,alternatingbetweentherstandsecondphoneline.
Forexample,aDDpathwithan893Amodulesetfordailytestreportfrequency
sends a test report through phone line 1 one day and phone line 2 the next day.
Ifthe893AoptionissettoYES,enteruptoa3-digitprextobedialedbeforethe
secondphonenumber.Ifnoprexisentered,thesecondphonenumberisdialedas
originally entered.
3.27
ALARM SWITCH: 1
Alarm Switch
This prompt displays for DD or CID Communication Types.
Enter the number of attempts to send an alarm message before switching to the next
path.Rangeisfrom1to10.Allnon-alarmmessagesaresentfor10attemptsonthe
dialer before a switch is initiated. If the path immediately following this channel is
not a backup path, this option has no effect. Default is 1.
3.28
DUPLICATE ALARMS
Duplicate Alarms
ThispromptdisplaysforBACKUPpaths.IfYesisselected,thecurrentbackuppath
duplicates all alarms occurring on its group primary path. Default is No.
D E
O A B C
NO YES SHARED
NO YES
-
2ND LINE PREFIX: