COMPLIANCE
XR2500F Installation Guide Digital Monitoring Products
39
COMPLIANCE
UL 985 NFPA 72 (Chapter 2) Specications
Household Fire Warning System Units
37.1 Bell Output Denition
The Model XR2500F panel Bell Output must be programmed to operate steady on burglary alarms and pulsed
or temporal on re alarms. See the XR500 Series Programming Guide (LT-0679).
37.2 Audible Devices
At least one listed audible device rated to operate over the voltage rate of 11.7 VDC to 12.8 VDC and rated
at 85 DB minimum must be used.
37.3 Auxiliary Circuits
At least one re alarm initiating device shall be used on the system. If the voltage for the device is applied
by the control unit the re alarm initiating device shall be rated to operate over the range of 11.5 VDC to
12.7 VDC.
37.4 Bell Cutoff
The Bell Cutoff time cannot be less than ve minutes. See the XR500 Series Programming Guide (LT-0679).
California State Fire Marshal Specications
38.1 Bell Output Denition
The Model XR2500F panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal, or California School Code on re alarms. See the XR500 Series Programming Guide (LT-0679).
New York City (MEA) Specications
39.1 Introduction
The programming and installation specications contained in this section must be completed when installing
the XR500 Series panel for New York City (MEA) re alarm installations that provide a digital dialer with
network IP communication as backup. Fire alarm installations that use two digital dialer telephone lines do
not need to comply with these specications.
39.2 Digital Dialer and Network Communication
When used with a central ofce communicator or a transmitter, the installation and operation of the
equipment and devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as
the primary communicator (using telephone line) with network IP communication as backup or secondary
means of communication. It shall have the capability of transmitting separate and distinct signals to
indicate manual pull station alarm, automatic detection alarm, sprinkler waterow alarm, supervisory signal
indications and trouble indications.
39.3 Wiring
All wiring must be in accordance with NEC, ANSI, and NFPA 70. All network cabling must be installed in
accordance with NFPA 70 for communication circuits.
39.4 Communication Programming
For digital dialer communication with supervised network backup, program the following:
COMM TYPE = NET
SECOND LINE = DD
RECEIVER 1
ALARMS = YES
FIRST PHONE NUMBER = Central Station Receiver Phone Number
RECEIVER 2
ALARMS = YES
FIRST PHONE NUMBER = Central Station Receiver Phone Number
See the XR500 Series Programming Guide (LT-0679).
39.5 Additional Requirements
Program and install the equipment to comply with NFPA basic re requirements. Refer to the Universal UL
and NFPA Fire Alarm Specications and UL 864 NFPA 72 (Chapter 9) Specications earlier in this document.