Installation guide
Digital Monitoring Products XR2500F Installation Guide
36
COMPLIANCE
XR2500F Installation Guide Digital Monitoring Products
37
COMPLIANCE
UL 864 NFPA 72 (Chapter 9) Specications
Control Units for Fire-Protective Signaling Systems
36.1 Zone Restoral Reports
The Restoral Reports option must be selected as YES or Disarm. See the XR500 Series Programming Guide
(LT-0679).
36.2 Power Fail Delay
The Power Fail Delay option must be selected as required by the service of the panel. For Central Station
service: 6-12, for Remote Station service: 12-15. See the XR500 Series Programming Guide (LT-0679).
36.3 Sprinkler Supervisory
Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The
last three characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual
Phone Line Module must be used on all sprinkler supervisory systems.
36.4 DACT Systems
Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893A Dual
Phone Line Module is used to provide two phone line connections to the system. The 2ND Phone Line
communication option must be selected as DD. See the XR500 Series Programming Guide (LT-0679).
Two different phone numbers must be programmed for digital communication. See the XR500 Series
Programming Guide (LT-0679). The Test Time option must be programmed so that the XR2500F sends a report
every 24 hours. See the XR500 Series Programming Guide (LT-0679).
36.5 Local Protective Signaling Systems
The DMP Model 865, 866, or 867 Notication Circuit Module must be used on the bell circuit for detection of
shorts and grounds. See sections 32.1 to 32.2 in this guide for wiring diagrams. Model 690/690F, 790/790F,
793, 630F keypads that are used to display troubles for local re alarm systems must be installed within a
DMP Model 777 with 777S 1.0” spacer. Any burglary or other off premises communication must be done with
the Model 893A Dual Phone Line Module. For local commercial re installations, the 893A is required.
36.6 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. See section 16.9 in this guide for standby battery
calculations. Two Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone
connections. See the D127 Installation Instruction sheet for wiring details. A DMP Model 893A is used to
provide two line dialer communication.
36.7 Fire Protective Signaling Systems
The XR2500F Panel must be programmed as described below for Fire Protective Signaling Systems using
Internet or Intranet network alarm communication.
• UL AA must be programmed as NO
• SUB CODE must be programmed as YES
• CHECKIN must be programmed as 1
• RETRY TIME must be programmed as 1
• FAIL TIME must be programmed as 1
• NET TRBL must be programmed as YES