Installation guide

Digital Monitoring Products XR2500F Installation Guide
36
COMPLIANCE
XR2500F Installation Guide Digital Monitoring Products
37
COMPLIANCE
Universal UL and NFPA Fire Alarm Specications
35.1 Introduction
The programming and installation specications contained in this section must be completed when installing
the Model XR2500F in accordance with any of the UL or NFPA re standards. Additional specications may be
required by a particular standard.
35.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
35.3 Transformer
A wire-in transformer should be used. Use the supplied 16 VAC 56 VA transformer. The transformer must be
mounted within 20 feet of the panel and connected by conduit.
35.4 End-of-Line Resistor
The DMP Model 310 1K Ohm EOL resistor should be used on all 1K Ohm EOL re zones.
35.5 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See the
XR500 Series Programming Guide (LT-0679).
35.6 Fire Display
The Status List Display must include at least one keypad that displays troubles and alarms on re type zones.
See the XR500 Series Programming Guide (LT-0679).
35.7 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is specically provided for that purpose.
35.8 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular
maintenance by the installing alarm company and frequent testing by the end user is essential. Offering a
maintenance program and acquainting the user with the correct procedures for system use and testing is
also the responsibility of the installing alarm company.
35.9 Audible Alarm
Fire Type zones must be programmed to activate an audible alarm. The Bell Action for Fire Type zones must
not be programmed as “N”. See the XR500 Series Programming Guide (LT-0679).
35.10 Fire Zone Programming
If a retard delay is used on a waterow zone, it cannot exceed 90 seconds and any retard delay in the
waterow initiating devices must be subtracted from the 90 seconds allowed. See the XR500 Series
Programming Guide (LT-0679). The retard delay should not be used on a zone with smoke detectors.
35.11 Style D Zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Style D zones to the
Model XR2500F. See the 869 Installation Guide (LT-0186) and sections 29.2 and 37.2 of this guide for wiring
information.
35.12 Video Option
The Video option must be selected as NO when any re protection is connected to the XR2500F. See the
XR500 Series Programming Guide (LT-0679).
35.13 UL Listed Receivers
Use the DMP SCS-1/SCS-1R (SDLC), Sur-Gard SG-HLR2-DG (CID), FBII CP220PB (CID), and Osborne-Hoffman
Quick-Alert (CID) receivers.