Installation guide

Digital Monitoring Products XR2500F Installation Guide
34
COMPLIANCE
XR2500F Installation Guide Digital Monitoring Products
35
COMPLIANCE
UL 365 and 609 Specications
Police Station Connected and Local Burglar Alarm Units and Systems
33.1 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See the
XR500 Series Programming Guide (LT-0679).
33.2 Entry Delay
The maximum entry delay used must not be more than 60 seconds. See the XR500 Series Programing Guide
(LT-0679).
33.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds. See the XR500 Series Programming Guide
(LT-0679).
33.4 Grade A Bell
A Grade A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
33.5 Bell Cutoff
The Bell Cutoff time cannot be less than 15 minutes. See the XR500 Series Programming Guide (LT-0679).
33.6 Automatic Bell Test
The Automatic Bell Test option must be programmed as YES. See the XR500 Series Programming Guide
(LT-0679).
33.7 Line Security for Police Connect
Basic line security is provided when the Model XR2500F is congured as a dialer system.
33.8 High Line Security
High Line Security is provided when congured as a NET system using an XR500N panel or an XR500 panel
with an iCOM™ Internet Alarm Router. The NET Check-in time must be set from 01 to 06 minutes or AA.
When a dialer is required for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A) is
required. When the check-in time is set to a number less than 200 seconds, an attack resistant enclosure is
not required. See sections 3.2, 3.2.1, and 3.3 of the XR500 Series Programming Guide (LT-0679).
To provide High Line Encrypted security, install an XR500E panel or an XR500 panel with an iCOM-E™
Encrypted Network Alarm Router.
For high line security operation, communication between the Premise and Supervising Station provides 128
bit encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm
Router.
UL 294 Specications
34.1 Panel Designation
The XR2500F is designated as a stand alone unit.
34.2 Compatible Devices
The following devices are compatible with the XR2500F panels.
Access Control
733 Wiegand Interface Module Proximity reader connector
734 Wiegand Interface Module Programmable proximity reader connector
OP-08CB Motion Detector Infrared sensor.
* PB-2 REX Button Exit control push button
PP-6005B Proxpoint Plus® Reader Proximity reader
MP-5365 Miniprox® Reader Slimline proximity reader
PR-5455 ProxPro® II Reader Long range reader with sounder
MX-5375 Maxi-Prox™ Reader Long range reader compatible with 1351 Prox Pass
* This device has not been investigated by UL and shall not be used in UL installations.