Installation guide

Digital Monitoring Products XR2500F Installation Guide
32
COMPLIANCE
XR2500F Installation Guide Digital Monitoring Products
33
COMPLIANCE
UL 1023 Specications
Household Burglar-Alarm System Units
30.1 Audible Devices
At least one listed audible device (Ademco AB12M) rated to operate over the voltage rate of 11.7 VDC to
12.8 VDC and rated at 85 DB minimum must be used.
30.2 Auxiliary Circuits
At least one burglary alarm initiating device shall be used on the system. If the voltage for the device is
applied by the control unit the burglary alarm initiating device shall be rated to operate over the range of
11.5 VDC to 12.7 VDC.
30.3 Bell Cutoff
The Bell Cutoff time cannot be less than ve minutes. See the XR500 Series Programming Guide (LT-0679).
30.4 Entry Delay
The maximum entry delay used must not be more than 45 seconds. See the XR500 Series Programming Guide
(LT-0679).
30.5 Exit Delay
The maximum exit delay used must not be more than 60 seconds. See the XR500 Series Programming Guide
(LT-0679).
30.6 Weekly Test
The product should be tested weekly.
UL 1635 Specications
Digital Burglar Alarm Communicator System Units
31.1 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See the
XR500 Series Programming Guide (LT-0679).
31.2 Digital Dialer Telephone Number
Both programmed telephone numbers must begin with a P. See the XR500 Series Programming Guide
(LT-0679).
31.3 Test Time
The Test Time option must be programmed so that the XR2500F sends a report once every 24 hours. See the
XR500 Series Programming Guide (LT-0679).
31.4 Closing Wait
The Closing Wait option must be programmed YES. See the XR500 Series Programming Guide (LT-0679).
31.5 Entry Delay
The maximum entry delay used must not be more than 60 seconds. See the XR500 Series Programming Guide
(LT-0679).
31.6 Exit Delay
The maximum exit delay used must not be more than 60 seconds. See the XR500 Series Programming Guide
(LT-0679).