Universal UL Burglary Specications
28.1 Introduction
The programming and installation specications contained in this section must be completed when installing
the XR2500F panel in accordance with any of the UL burglary standards. Additional specications may be
required by a particular standard.
28.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70, UL 681. All transformer wires must be installed in
conduit.
28.3 Control Outside of Protected Area
A Potter EVD or Sentrol 5402 should be used in place of a lined cabinet when the panel is installed outside
of the protected area. Front and rear tamper switches are required. Refer to the system wiring diagram
and Figure 2.
28.4 Police Station Phone Numbers
The digital dialer telephone number programmed for communication must not be a police station phone
number.
28.5 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular
maintenance by the installing alarm company and frequent testing by the end user is essential. Offering a
maintenance program and acquainting the user with the correct procedures for system use and testing is
also the responsibility of the installing alarm company.
28.6 UL Listed Receivers
UL has veried operation with the DMP SCS-1 and SCS-1R, Sur-Gard SG-HLR2-DG, FBII CP220PB, Osborne-
Hoffman Quick-Alert, and Radionics D6500 receivers. It is the installer’s responsibility to verify compatibility
between the XR2500F and the receiver used during installation. The installer shall verify the compatibility
of the receiver and the system on a yearly basis.
Area Information
29.1 Ownership
The control unit system shall be under one ownership.
29.2 Annunciation
The System shall be installed so that when arming any area from any keypad, the local bell shall annunciate.
29.3 Trouble Display
The Status List programming shall be set to annunciate all trouble messages at all keypads. See the XR500
Series Programming Guide (LT-0679).
29.4 Closing Wait
The Closing Wait option must be programmed YES. See the XR500 Series Programming Guide (LT-0679).
29.5 Local Bell Supervision
When a local bell is employed, the power supply for the bell shall be under 24-hour protection. Proper
personnel for maintenance or security of the system shall be able to disarm that area.