12.1 Power Supply
Transformer Input: Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA
Standby Battery: 12 VDC, 1.0 Amps Max. charging current
Auxiliary: 12 VDC output at 1.5 Amp Max
Bell Output: 12 VDC at 1.5 Amp Max
Note: The combined Auxiliary and Bell outputs total cannot exceed 3 Amps with a 56 VA Transformer.
All circuits are inherent Power Limited except the red battery wire and AC terminal.
Note: For UL installations, the total current combined from Auxiliary and Bell Power cannot exceed:
1.3 Amps with a 50 VA transformer, 1.0 Amp Max for Auxiliary Power
1.9 Amps with a 56 VA transformer, 1.0 Amp Max for Auxiliary Power and 1.5 Amp Max for Bell.
12.2 Communication
Built-in dialer communication to DMP Model SCS-1/SCS-1R Receivers
Built-in Contact ID communication to non-DMP receivers
893A Dual Phone Line Module with phone line supervision
Can operate as a local panel
12.3 Panel Zones
Eight 1k Ohm EOL burglary zones (zones 1 to 8). Connect to 869 Class A module for burglary applications.
Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10).
Note: Use the supplied DMP Model 311 1k Ohm and DMP Model 301 3.3k Ohm resistors.
12.4 Keypad Bus
You can connect up to 16 of the following supervised keypads and expansion modules to the keypad bus:
Alphanumeric Fire Command Centers or keypads
Four- and/or single-zone expansion modules
Single-zone detectors
Access control modules
12.5 LX-Bus™
You can connect the following devices to the LX-Bus™ provided by the DMP 481 (supplied) or by the 462N,
481, 462P, 462FM, and 472 Interface Cards up to the maximum number of LX-Bus™ addresses. See Accessory
Devices.
Model 521LX or 521LXT Smoke Detectors with CleanMe
Model SLRLX Smoke Detectors
Sixteen-, eight-, four- and/or single-zone expansion modules
Single-zone detectors
Relay output expansion modules
Graphic annunciator modules
12.6 Outputs
The XR2500F provides two pre-installed Model 305 Single Pole, Double Throw (SPDT) relay outputs, each
rated 1 Amp at 30 VDC resistive (power limited sources only).
The XR2500F also provides four open collector outputs rated for 50mA each. The open collector outputs
provide ground connection for a positive voltage source. A Model 300 Output Harness is required to use
these outputs and may be connected to a Model 860 Relay Output Module.