Installation guide

XR500 Series Installation Guide Digital Monitoring Products
39
WIRInG dIaGRams
36.4 Cellular Backup Installation for Derived Channel Burglary
J6
Interface
Card
Expansion
Connector
Output Header J2 All outputs must be
connected to devices located within the
same room as the panel.
XR500 Series
Command Processor™
Panel
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDREDYEL GRNBLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+Z9– Z10+Z10–AC –B GND GND GNDGND
K6 K7
J3
Phone Line
J10
J22
Battery
Start
J23
J21
J8
PROG
J4
Ta mper
J16
Reset
J11
J2
J1
Cellular
Transceiver
= Supervised Circuit
S
1 2 3 4 5 6
Panel Auxiliary Power - Terminal 7
Note 1
Note 1
Telco Jack
Panel Common - Terminal 10
Supervisory Zone Input - Terminal 13
893A
Auxiliary
Power
Supply
S S
S
S
S
S
S
The Secure-Com Cellular
System must be connected
to a separate power supply.
Use only for supplementary
(backup communication).
Cellular Data
Interface
Note 1: Use EOL Termination Assembly P/N
21024-0001 (2.2k Ohm 1/2 W Resistor).
Use EOL Termination
Assembly P/N 21024-0003
(590 Ohm 1/2 W Resistor)
DCX Systems
STU-2Z
R
L
X
Auxiliary Power Supply must be
regulated, UL Listed for Fire
Protective Signaling Service.
Power Supplies must have battery backup.
Interfacing STU-2Z/STU-4Z to the XR500 Series Panels
The STU-2Z or STU-4Z may only be used in conjunction with
telephone systems that support DCX Systems Derived Channel
multiplex network. The STU-2Z or STU-4Z can only be installed in a
DMP Model 350 enclosure.
Burglary
The STU-2Z and STU-4Z are cross listed with the XR500 Series panels
asanaccessoryforStandrdCentralStationBurglarAlarm.For
Standard line security, the following conditions must be met:
• ThepanelmustbeinstalledandprogrammedtomeetStandard
line security burglary alarm system requirements.
• Thepanelmustbeinstalledandprogrammedforreportingall
alarm conditions through the integral DACT to the same central
station that monitors the STU-2Z or STU-4Z.
• TheSTU-2ZorSTU-4Zmustbemountedinthepanelenclosure
and wired according to Section 32.4 above.
• Onceinstalled,thecentralstationmustenable2-minuteoff-hook
polling of the STU-2Z or STU-4Z.
Supplementary Reporting (for Commercial Burglar Alarm
Applications)
The two zones of the STU-2Z or the four zones of the STU-4Z may
be used for supplementary reporting by meeting the following
requirements.
1. Program Relay Output #1 for all alarm conditions that are
required to report alarm on Zone 1 of the STU-2Z or STU-4Z.
2. Program Relay Output #2 for all alarm conditions that are
required to report alarm on Zone 2 of the STU-2Z or STU-4Z.
3. Wire the normally-open terminals of Relay Output #1 to Terminal 1 of the
STU-2Z or STU-4Z.
4. Wire the common terminal of Relay Output #1 to Terminal 2 of the STU-2Z
or STU-4Z.
5. Wire the normally-open terminal of Relay Output #2 to Terminal 3 of the
STU-2Z or STU-4Z.
6. Wire the common terminal of Relay Output #2 to Terminal 2 of the STU-
2Z or STU-4Z.
Commercial Fire
When the XR500 Series panel is used as a Central Station Alarm Commercial
FireSystemwithonetelephoneline,inconjunctionwithDCXSystemsSTU-2Z
or STU-4Z, the following conditions must be met:
• Thepanelmustbeinstalledandprogrammedtomeetcommercialre
(reporting) systems requirements.
• Thepanelmustbeinstalledandprogrammedforreportingallalarm
conditions and trouble conditions to the same central station that
monitors the STU-2Z or STU-4Z.
• TheSTU-2ZorSTU-4Zmustbemountedinthepanelenclosureandwired
according to Section 32.4 above.
• Onceinstalled,thecentralstationmustenable2-minuteoff-hookpolling
of the STU-2Z or STU-4Z.
Installing the STU-2Z/STU-4Z into the DMP Model 350
Enclosure
The STU board is mounted in the left side of the DMP Model 350 enclosure by
slipping the optional corner mounting bracket over the edge of the enclosure.
Use DCX Part # 27074-002 (2Z) or Part # 27078-001 (4Z). Connect the STU
power wires and telco cables to the panel terminals and RJ31X as shown in
Section 32.4 above.