Installation guide
XR500 Series Installation Guide Digital Monitoring Products
37
WIRInG dIaGRams
36.2 Multiple Notication Circuit Modules for Zoned Annunciation
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDREDYEL GRNBLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+Z9- Z10+ Z10-AC -B GND GND GNDGND
K6 K7
J3
J10
J22
Battery
Start
J23
J21
J8
J4
Ta mper
J16
Reset
J11
J2
J1
J6
Interface
Card
Expansion
Connector
XR500 Series
Command Processor™
Panel
J2 Output Header
All outputs must be located
within the same room as
the control panel.
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
866 Module
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In -
6 Bell Out A +
10 Bell Trouble
11 Bell Trouble
865 Module
Normal/Silence Switch
10K EOL
DMP Model 308
UL Listed,
Polarized
Notification
Appliances
Style W
UL Listed,
Polarized
Notification
Appliances
Style y
24 VDC
5 Amp
Maximum
Power Supply Trouble
Contacts N/C
7 Bell Out A -
8 Bell Out B +
9 Bell Out B -
504-24
Power
Supply
+ -
Zone 1 Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
1K EOL
+
-
+
-
Auxiliary Power Supply must be
regulated, UL Listed for Fire Protective
Signaling Service. Power Supplies must
have battery backup.
S
S
S
S
S
S
S
S
S
S
S
S
To additional Zone 1 Notification Circuit
Modules.
Install up to a maximum of twenty-five
866 Modules by using the relay outputs
available on the XR500 Series panel.
All modules must be installed in a
340FC, 349, or 350 Enclosure connected
by no more than 20 feet of conduit.
Zone 2 Notification
Circuit Module
DMP Model 865
26mA @ 12 VDC
The Auxiliary Power Supply and
Notification Circuit Module trouble
contact zone must be programmed as
a Supervisory Type zone and must be
selected for display in the keypad
status list. See section 12.6 in the
Programming Guide (LT-0679).
Note: If an auxiliary power supply is
not used, terminals 3 and 4 can be
jumpered together to supply Bell
Power from the XR500 Series panel.
10K EOL
DMP Model 308
UL Listed,
Polarized
Notification
Appliances
Style W
24 VDC 5
Amp
Maximum
Power Supply Trouble
Contacts N/C
24 VDC
5 Amp
Maximum
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
866 Module
Normal/Silence Switch
Common Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
1K EOL
504-24
Power
Supply
+ -
S
S S
SS
S
504-24
Power
Supply
+ -
S
S
S
To additional notification
circuit modules.
Each 866 Notification Appliance
Circuit Module in alarm draws up to
30mA through its Te rminal 3 Alarm
Input and 45mA from its Te rminal 1
Aux Power Input.
Each 865 Notification Appliance
Circuit Module in alarm draws up to
59mA through its Te rminal 3 Alarm
Input and 26mA from its Te rminal 1
Aux Power Input.
S
= Supervised Circuit
Zone 1 Output
Relay 1
N/O
Orange
Zone 2 Output
Relay 2
N/O
Orange/White
Relay 1 and 2
Common
Gray
R
L
X