Installation guide

XR500 Series Installation Guide Digital Monitoring Products
37
WIRInG dIaGRams
36.2 Multiple Notication Circuit Modules for Zoned Annunciation
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDREDYEL GRNBLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+Z9- Z10+ Z10-AC -B GND GND GNDGND
K6 K7
J3
J10
J22
Battery
Start
J23
J21
J8
J4
Ta mper
J16
Reset
J11
J2
J1
J6
Interface
Card
Expansion
Connector
XR500 Series
Command Processor™
Panel
J2 Output Header
All outputs must be located
within the same room as
the control panel.
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
866 Module
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In -
6 Bell Out A +
10 Bell Trouble
11 Bell Trouble
865 Module
Normal/Silence Switch
10K EOL
DMP Model 308
UL Listed,
Polarized
Notification
Appliances
Style W
UL Listed,
Polarized
Notification
Appliances
Style y
24 VDC
5 Amp
Maximum
Power Supply Trouble
Contacts N/C
7 Bell Out A -
8 Bell Out B +
9 Bell Out B -
504-24
Power
Supply
+ -
Zone 1 Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
1K EOL
+
-
+
-
Auxiliary Power Supply must be
regulated, UL Listed for Fire Protective
Signaling Service. Power Supplies must
have battery backup.
S
S
S
S
S
S
S
S
S
S
S
S
To additional Zone 1 Notification Circuit
Modules.
Install up to a maximum of twenty-five
866 Modules by using the relay outputs
available on the XR500 Series panel.
All modules must be installed in a
340FC, 349, or 350 Enclosure connected
by no more than 20 feet of conduit.
Zone 2 Notification
Circuit Module
DMP Model 865
26mA @ 12 VDC
The Auxiliary Power Supply and
Notification Circuit Module trouble
contact zone must be programmed as
a Supervisory Type zone and must be
selected for display in the keypad
status list. See section 12.6 in the
Programming Guide (LT-0679).
Note: If an auxiliary power supply is
not used, terminals 3 and 4 can be
jumpered together to supply Bell
Power from the XR500 Series panel.
10K EOL
DMP Model 308
UL Listed,
Polarized
Notification
Appliances
Style W
24 VDC 5
Amp
Maximum
Power Supply Trouble
Contacts N/C
24 VDC
5 Amp
Maximum
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
866 Module
Normal/Silence Switch
Common Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
1K EOL
504-24
Power
Supply
+ -
S
S S
SS
S
504-24
Power
Supply
+ -
S
S
S
To additional notification
circuit modules.
Each 866 Notification Appliance
Circuit Module in alarm draws up to
30mA through its Te rminal 3 Alarm
Input and 45mA from its Te rminal 1
Aux Power Input.
Each 865 Notification Appliance
Circuit Module in alarm draws up to
59mA through its Te rminal 3 Alarm
Input and 26mA from its Te rminal 1
Aux Power Input.
S
= Supervised Circuit
Zone 1 Output
Relay 1
N/O
Orange
Zone 2 Output
Relay 2
N/O
Orange/White
Relay 1 and 2
Common
Gray
R
L
X