Installation guide

Digital Monitoring Products XR500 Series Installation Guide
36
WIRInG dIaGRams
Wiring Diagrams
36.1 Multiple Notication Circuit Modules
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDREDYEL GRNBLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+Z9– Z10+ Z10–AC –B GND GND GNDGND
K6 K7
J3
J10
J22
Battery
Start
J23
J21
RS-232
J8
J4
Ta mper
J16
Reset
J11
J2
J1
J6
Interface
Card
Expansion
Connector
XR500 Series
Command Processor™
Panel
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
866
Module
Normal/Silence Switch
10K EOL
DMP Model 308
UL Listed,
Polarized
Notification
Appliances
Style W
UL Listed,
Polarized
Notification
Appliances
Style Z
24 VDC 5
Amp
Maximum
Power Supply Tr ouble
Contacts N/C
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In -
6 Bell Out A +
10 Bell Trouble
11 Bell Trouble
865
Module
Normal/Silence Switch
7 Bell Out A -
8 Bell Out B +
9 Bell Out B -
+ -
Notification Circuit Module
DMP Model 866
45mA @12 VDC
To additional 866 Notification Circuit Modules. Up to a maximum of twenty-five
866 Modules on the XR500 Series panel. All modules must be installed in a
340FC, 349, or 350 enclosure connected by no more than 20 feet of conduit.
S
24 VDC 5
Amp
Maximum
Power Supply
Trouble
Contacts N/C
Auxiliary
Power
Supply
+ -
S
1K EOL
+
-
+
-
Each 866 Notification Appliance
Circuit Module in alarm draws up to
30mA through its Te rminal 3 Alarm
Input and 45mA from its Te rminal 1
Aux Power Input.
Each 865 Notification Appliance
Circuit Module in alarm draws up to
59mA through its Te rminal 3 Alarm
Input and 26mA from its Te rminal 1
Aux Power Input.
The Auxiliary Power Supply and
Notification Circuit Module trouble
contact zone must be programmed as
a Supervisory Type zone and must be
selected for display in the keypad
status list. See section 12.6 in the
Programming Guide (LT-0679).
S= Supervised Circuit
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
Auxiliary
Power
Supply
Auxiliary Power Supply must be regulated, UL Listed for Fire Protective
Signaling Service. Power Supplies must have battery backup.
Note: If an auxiliary power supply is not used, terminals 3 and 4 can be
jumpered together to supply Bell Power from the XR500 panel.
Notification Circuit Module
DMP Model 865
25mA @12 VDC
Optional Notification
Module Installation
R
L
X