31.5 Detect Wireless Jamming
TheDetectWirelessJammingoptionmustbeprogrammedYES.SeetheXR500SeriesProgrammingGuide(LT-0679).
31.6 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed. See the XR500 Series
ProgramingGuide(LT-0679).
31.7 Wireless Supervision Time
TheZoneInformationSupervisionTimemustbe240minutes.SeetheXR500SeriesProgramingGuide(LT-0679).
31.8 Wireless Fire Verication
Whenused,theModel1161and1162wirelesssmokedetectorsmustnotbeprogrammedasFireVerication(FV)
zonetype.SeetheXR500SeriesProgramingGuide(LT-0679).
California State Fire Marshal Specications
32.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal,orCaliforniaSchoolCodeonrealarms.SeetheXR500SeriesProgrammingGuide(LT-0679).
New York City (MEA) Specications
33.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingthe
XR500SeriespanelforNewYorkCity(MEA)realarminstallationsthatprovideadigitaldialerwithnetworkIP
communicationasbackup.Firealarminstallationsthatusetwodigitaldialertelephonelinesdonotneedtocomply
withthesespecications.
33.2 Digital Dialer and Network Communication
Whenusedwithacentralofcecommunicatororatransmitter,theinstallationandoperationoftheequipmentand
devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as the primary communicator
(using telephone line) with network IP communication as backup or secondary means of communication. It shall
have the capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
detectionalarm,sprinklerwaterowalarm,supervisorysignalindicationsandtroubleindications.
33.3 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI,andNFPA70.Allnetworkcablingmustbeinstalledinaccordance
withNFPA70forcommunicationcircuits.
33.4 Communication Programming
Fordigitaldialercommunicationwithsupervisednetworkbackup,programthefollowing:
COMM TYPE = NET
SECOND LINE = DD
RECEIVER 1
ALARMS = YES
FIRSTPHONENUMBER=CentralStationReceiverPhoneNumber
RECEIVER 2
ALARMS = YES
FIRSTPHONENUMBER=CentralStationReceiverPhoneNumber
SeetheXR500SeriesProgrammingGuide(LT-0679).
33.5 Additional Requirements
ProgramandinstalltheequipmenttocomplywithNFPAbasicrerequirements.RefertotheUniversalFireAlarm