Installation guide
XR500 Series Installation Guide Digital Monitoring Products
33
ComPlIanCe
31.5 Detect Wireless Jamming
TheDetectWirelessJammingoptionmustbeprogrammedYES.SeetheXR500SeriesProgrammingGuide(LT-0679).
31.6 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed. See the XR500 Series
ProgramingGuide(LT-0679).
31.7 Wireless Supervision Time
TheZoneInformationSupervisionTimemustbe240minutes.SeetheXR500SeriesProgramingGuide(LT-0679).
31.8 Wireless Fire Verication
Whenused,theModel1161and1162wirelesssmokedetectorsmustnotbeprogrammedasFireVerication(FV)
zonetype.SeetheXR500SeriesProgramingGuide(LT-0679).
California State Fire Marshal Specications
32.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal,orCaliforniaSchoolCodeonrealarms.SeetheXR500SeriesProgrammingGuide(LT-0679).
New York City (MEA) Specications
33.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingthe
XR500SeriespanelforNewYorkCity(MEA)realarminstallationsthatprovideadigitaldialerwithnetworkIP
communicationasbackup.Firealarminstallationsthatusetwodigitaldialertelephonelinesdonotneedtocomply
withthesespecications.
33.2 Digital Dialer and Network Communication
Whenusedwithacentralofcecommunicatororatransmitter,theinstallationandoperationoftheequipmentand
devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as the primary communicator
(using telephone line) with network IP communication as backup or secondary means of communication. It shall
have the capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
detectionalarm,sprinklerwaterowalarm,supervisorysignalindicationsandtroubleindications.
33.3 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI,andNFPA70.Allnetworkcablingmustbeinstalledinaccordance
withNFPA70forcommunicationcircuits.
33.4 Communication Programming
Fordigitaldialercommunicationwithsupervisednetworkbackup,programthefollowing:
COMM TYPE = NET
SECOND LINE = DD
RECEIVER 1
ALARMS = YES
FIRSTPHONENUMBER=CentralStationReceiverPhoneNumber
RECEIVER 2
ALARMS = YES
FIRSTPHONENUMBER=CentralStationReceiverPhoneNumber
SeetheXR500SeriesProgrammingGuide(LT-0679).
33.5 Additional Requirements
ProgramandinstalltheequipmenttocomplywithNFPAbasicrerequirements.RefertotheUniversalFireAlarm
SpecicationsandANSI/UL864NFPA72(Chapter9)Specicationsearlierinthisdocument.