32
ComPlIanCe
30.3 Sprinkler Supervisory
Anyzoneusedforsprinklersupervisorymustbeprogrammedwith“SPRINKLRXXX”asthezonename.Thelastthree
characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual Phone Line Module
must be used on all sprinkler supervisory systems.
30.4 DACT Systems
Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893A Dual Phone Line
Module is used to provide two phone line connections to the system. The 2ND Phone Line communication option must
beselectedasDD.SeetheXR500SeriesProgrammingGuide(LT-0679).
Two different phone numbers must be programmed for digital communication. See the XR500 Series Programming
Guide(LT-0679).TheTestTimeoptionmustbeprogrammedsothattheXR500Seriessendsareportevery24hours.
SeetheXR500SeriesProgrammingGuide(LT-0679).
30.5 Local Protective Signaling Systems
TheDMPModel865,866,or867NoticationCircuitModulemustbeusedonthebellcircuitfordetectionofshorts
and grounds. Any burglary or other off premises communication must be done with the Model 893A Dual Phone Line
Module.Forlocalcommercialreinstallations,the893Aisrequired.
30.6 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. See section 6.9 in this guide for standby battery calculations. Two
Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See the D127
Installation Instruction sheet for wiring details. A DMP Model 893A is used to provide two line dialer communication.
30.7 Fire Protective Signaling Systems using Internet/Intranet Networks
TheXR500SeriesCommandProcessor™PanelmustbeprogrammedasdescribedbelowforFireProtectiveSignaling
Systems using NET Communication Type or an iCOM™ Network Alarm Router for communication. Refer to the iCOM™
Network Alarm Router Installation Sheet (LT-0587) for more information.
• ULAAmustbeprogrammedasNO • RETRYTIMEmustbeprogrammedas1
• SUBCODEmustbeprogrammedasYES • FAILTIMEmustbeprogrammedas1
• CHECKINmustbeprogrammedas1 • NETTRBLmustbeprogrammedasYES
30.8 Combination Systems
Forcombinationreandburglarysystems,poweredburglarydevices(PIR,Glassbreak,etc.)mustbepoweredfroma
separate listed power supply (DMP Model 505-12). This requirement is not needed for non-powered burglary devices
(door contacts, etc.) which only connect to the zone input of zone expanders or keypads. Refer to Powered Burglary
Devices later in this document.
30.9 Remote Annunciators
AtleastoneModel630FRemoteAnnunciatormustbeusedonthesystem.Allrealarms,retroublesand
supervisoryalarmsortroublesmustbeannunciatedonlyonthe630F.Allburglaryalarmsortroublesmustonlybe
annunciatedonnon-rekeypads.SeeStatusListoptionsoftheXR500SeriesProgrammingGuide(LT-0679).
ANSI/UL 985 NFPA 72 (Chapter 2) Specications
Household Fire Warning System Units
31.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed or
temporalonrealarms.SeetheXR500SeriesProgrammingGuide(LT-0679).
31.2 Audible Devices
At least one listed audible device rated to operate over the voltage rate of 11.7 VDC to 12.8 VDC and rated at 85 DB
minimum must be used.
31.3 Auxiliary Circuits
Atleastonerealarminitiatingdeviceshallbeusedonthesystem.Ifthevoltageforthedeviceisappliedbythe
controlunittherealarminitiatingdeviceshallberatedtooperateovertherangeof11.5VDCto12.7VDC.
31.4 Bell Cutoff
TheBellCutofftimecannotbelessthanveminutes.SeetheXR500SeriesProgrammingGuide(LT-0679).