Installation guide
XR500 Series Installation Guide Digital Monitoring Products
31
ComPlIanCe
29.3 Transformer
A wire-in trans former should be used. Use the Model 322 wire-in 16 VAC 56 VA transformer or Model 327 plug-in
16 VAC 50 VA transformer installed inside an ES501 Enclosure with all wiring in conduit. The transformer must be
mounted within 20 feet of the panel and connected by conduit.
29.4 End-of-Line Resistor
TheDMPModel3101kOhmEOLresistorshouldbeusedonall1kOhmEOLrezones.
29.5 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See the XR500 Series
ProgrammingGuide(LT-0679).
29.6 Fire Display
TheStatusListDisplaymustincludeatleastonekeypadthatdisplaystroublesandalarmsonretypezones.See
theXR500SeriesProgrammingGuide(LT-0679).
29.7 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone number,
unlessthatphonenumberisspecicallyprovidedforthatpurpose.
29.8 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by the
installing alarm company and frequent testing by the end user is essential. Offering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
29.9 Audible Alarm
FireTypezonesmustbeprogrammedtoactivateanaudiblealarm.TheBellActionforFireTypezonesmustnotbe
programmedasN(None).SeetheXR500SeriesProgrammingGuide(LT-0679).
29.10 Fire Zone Programming
Ifaretarddelayisusedonawaterowzone,itcannotexceed90secondsandanyretarddelayinthewaterow
initiatingdevicesmustbesubtractedfromthe90secondsallowed.SeetheXR500SeriesProgrammingGuide
(LT-0679). The retard delay should not be used on a zone with smoke detectors.
29.11 Class A Style D Zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Class A Style D zones to the
ModelXR500Series.Seethe869InstallationGuide(LT-0186)andsections20.2and28.2ofthisguideforwiring
information.
29.12 Video Option
TheVideooptionmustbeselectedasNOwhenanyreprotectionisconnectedtotheXR500Series.SeetheXR500
SeriesProgrammingGuide(LT-0679).
29.13 Listed Receivers
UsetheDMPSCS-1R(SDLC),Sur-GardSG-HLR2-DG(CID),FBIICP220PB(CID),andOsborne-HoffmanQuick-Alert(CID)
receivers.
ANSI/UL 864 NFPA 72 (Chapter 9) Specications
Control Units for Fire-Protective Signaling Systems
30.1 Zone Restoral Reports
TheRestoralReportsoptionmustbeselectedasYESorDisarm.SeetheXR500SeriesProgrammingGuide(LT-0679).
30.2 Power Fail Delay
ThePowerFailDelayoptionmustbeselectedasrequiredbytheserviceofthepanel.ForCentralStationservice:
6-12,forRemoteStationservice:12-15.SeetheXR500SeriesProgrammingGuide(LT-0679).