Installation guide
XR500 Series Installation Guide Digital Monitoring Products
27
ComPlIanCe
ANSI/UL 636 Specications
Holdup Alarm Units
24.1 ANSI/UL 1610 Required
TheprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedinadditiontoANSI/UL
1610SpecicationswheninstallingaModel1142withaModelXR500Seriespanel.
24.2 1100X Wireless Receiver
The Model 1100X Wireless Receiver in conjunction with the Model 1142 Holdup Alarm Transmitter must be installed
in the system.
24.3 Wireless Supervision Time
The Zone Information Supervision Time must be a maximum of 240 minutes. See the XR500 Series Programming
Guide(LT-0679).
24.4 LED Display
The LED Operation option display must be set to NO when using a Model 1142 Holdup Alarm Transmitter. See the
XR500SeriesProgrammingGuide(LT-0679).
24.5 Jamming Detection
TheDetectWirelessJammingoptionmustbesettoYES.SeetheXR500SeriesProgrammingGuide(LT-0679).
24.6 Local Alarm
The Bell Action for a PN (Panic) type zone must be programmed as N (None). See the XR500 Series Programming
Guide(LT-0679).
24.7 Message to Transmit
The Armed Open and Armed Short messages for a PN (Panic) type zone must be programmed to A (Alarm). See the
XR500SeriesProgrammingGuide(LT-0679).
24.8 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
ANSI/UL 1635 Specications
Digital Burglar Alarm Communicator System Units
25.1 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See the XR500 Series
ProgrammingGuide(LT-0679).
25.2 Digital Dialer Telephone Number
BothprogrammedtelephonenumbersmustbeginwithaP.SeetheXR500SeriesProgrammingGuide(LT-0679).
25.3 Test Time
The Test Time option must be programmed so that the XR500 Series sends a report once every 24 hours. See the
XR500SeriesProgrammingGuide(LT-0679).
25.4 Closing Wait
TheClosingWaitoptionmustbeprogrammedYES.SeetheXR500SeriesProgrammingGuide(LT-0679).
ANSI/UL 365 Specications
Police Station Connected and Local Burglar Alarm Units and Systems
26.1 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See the XR500 Series
ProgrammingGuide(LT-0679).