Installation guide

Digital Monitoring Products XR500 Series Installation Guide
26
ComplianCe
23.11 Model 463G CELL with Dialer Backup, Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using CELL with DD (digital dialer) as a backup.
XR500 cellular communication is used as primary with a 6 minute check-in when armed, and a random check-in over
a 60 minute period when disarmed. The digital dialer sends a daily test signal and is backup.
Path 1 programming Path 2 programming
Comm Type: = CELL Comm Type: = DD
Path Type: = Primary Path Type: = Backup (operates as second method)
Test Rpt: = NO Test Rpt: = YES
Checkin: = 6 minute, or RND (random) Test Freq: = Daily
Fail Time: = 6 minute, or RND (random) Duplicate Alarms: = YES
Encrypt: = NO or YES*
Sub Code: = YES
*For Encrypted Line Security, program a Passphrase in Network Options.
23.12 Model 463G NET with CELL as Alternate Primary and Dialer Backup, Standard or
Encrypted Line Security
Standard or Encrypted Line Security is provided using NET communication with CELL as an alternate primary and
with digital dialer as a backup. XR500 network communication is used as primary with a 6 minute check-in when
armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and set to daily
test. Should the NET primary path become disabled, CELL adapts the same check-in time programmed for the
primary communication and becomes an alternate primary path. The dialer path is used as the backup if both NET
and CELL fail to receive acknowledgement from the receiver.
This method of operation causes the CELL alternate primary to adapt to the 6 minute NET primary check-in rate
when the NET primary is unavailable maintaining line supervision and precludes the need for a central station runner
to respond to the NET primary failure.
Path 1 programming Path 2 programming Path 3 programming
Comm Type: = NET Comm Type: = CELL Comm Type: = DD
Path Type: = Primary Path Type: = Backup (operates as
alternate primary)
Path Type: = Backup (operates
as second method)
Test Rpt: = NO Test Rpt: = YES Test Rpt: = YES
Checkin: = 6 minute, or RND (random) Test Freq: = Daily Test Freq: = Daily
Fail Time: = 6 minute, or RND (random) Checkin: = ADAPT Duplicate Alarms: = YES
Encrypt: = NO or YES* Encrypt: = NO or YES*
Sub Code: = YES Sub Code: = Shared
*For Encrypted Line Security, program a Passphrase in Network Options.
23.13 Model 463G NET with CELL as Backup and Adaptive Primary, Standard or
Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using NET communication and CELL as backup
and as needed adapts and takes over as primary. XR500 network communication is used as primary with a 6 minute
check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and
set to daily test. Should the primary path become disabled, the CELL adapts to a special 3 minute check-in time and
because of that check-in rate becomes the primary without the requirement of a backup. This method of operation
causes the CELL backup to adapt to the 3 minute check-in rate when the NET primary is unavailable becoming a
standalone primary without the need for a backup. This maintains line supervision and precludes the need for a
central station runner to respond to the NET primary failure.
Path 1 programming Path 2 programming
Comm Type: = NET Comm Type: = CELL
Path Type: = Primary Path Type: = Backup (operates as second method)
Test Rpt: = NO Test Rpt: = YES
Checkin: = 6 minute, or RND (random) Test Freq: = Daily
Fail Time: = 6 minute, or RND (random) Checkin: = ADAPT3
Encrypt: = NO or YES* Encrypt: = NO or YES*
Sub Code: = YES Duplicate Alarms: = YES
Sub Code: = Shared