Installation guide
XR500 Series Installation Guide Digital Monitoring Products
25
ComPlIanCe
ANSI/UL 1610 AND ANSI/UL 1076 Specications
Central-Station and Proprietary Burglar-Alarm Units
23.1 Opening/Closing Reports
TheOpening/ClosingReportsoptionmustbeprogrammedasYES.SeetheXR500SeriesProgrammingGuide
(LT-0679).
23.2 Closing Wait
TheClosingWaitoptionmustbeprogrammedYES.SeetheXR500SeriesProgrammingGuide(LT-0679).
23.3 Entry Delay
The maximum entry delay used must not be more than 60 seconds when using Model 350A Attack Resistant Housing.
SeetheXR500SeriesProgrammingGuide(LT-0679).
23.4 Exit Delay
Themaximumexitdelayusedmustnotbemorethan60seconds.SeetheXR500SeriesProgrammingGuide
(LT-0679).
23.5 Proprietary Dialer
TheModelXR500Seriesprovidesproprietaryservicewhenconguredasadigitaldialer.
23.6 DACT Central Station
DACT Central Station service can be provided under by adding an Ademco AB12M bell and bell housing and placing
the Model XR500 Series panel into Model 350A Attack Resistant Housing.
23.7 Bell Cutoff
TheBellCutofftimecannotbelessthan15minutes.SeetheXR500SeriesProgrammingGuide(LT-0679).
23.8 Standard or Encrypted Line Security
StandardLineSecurityisprovidedwhenconguredasaPath1NETsystemusinganXR500NpaneloranXR500
panel with an iCOM™ Network Alarm Router (232). The NET Check-in time must be set to 06 minutes or RDM. When
programmed for Standard Line Security, Exit Time Restart is disabled. When a dialer is required for 06 minute
check-in time, an attack resistant enclosure (DMP Model 350A) is required. When the check-in time is set to a
number less than 200 seconds, an attack resistant enclosure is not required. See sections 3.2, 3.2.1, and 3.3 of the
XR500SeriesProgrammingGuide(LT-0679).
To provide Encrypted Line security, install an XR500E panel or an XR500 panel with an iCOM-E™ Encrypted Network
Alarm Router.
ForEncryptedLinesecurityoperation,communicationbetweenthePremiseandSupervisingStationprovides128bit
encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm Router.
The Model XR500 Series Protected Premises Control Unit is suitable for Standard Line Security service when
conguredforNETcommunicationwithSCS-1Rreceivingsystem.Thiscongurationisapprovedforthefollowing:
AMCX - Central Station Alarm Units
APOU - Proprietary Alarm Units
23.9 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
23.10 Model 463G CELL Only, Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using CELL with no backup. XR500 cellular
communication is used as primary with a 3 minute check-in when armed or disarmed.
Path 1 programming
Comm Type: = CELL Checkin: = 3 minute
Path Type: = Primary FailTime:=3minute
Encrypt: = NO or YES* Test Rpt: = NO
Sub Code: = NO or YES
*ForEncryptedLineSecurity,programaPassphraseinNetworkOptions.