Installation guide
Digital Monitoring Products XR500 Series Installation Guide
24
ComPlIanCe
Area Information
21.1 Ownership
The control unit system shall be under one ownership.
21.2 Annunciation
The System shall be installed so that when arming any area from any keypad, the local bell shall annunciate.
21.3 Trouble Display
The Status List programming shall be set to annunciate all trouble messages at all keypads. See the XR500 Series
ProgrammingGuide(LT-0679).
21.4 Closing Wait
TheClosingWaitoptionmustbeprogrammedYES.SeetheXR500SeriesProgrammingGuide(LT-0679).
21.5 Local Bell Supervision
When a local bell is employed, the power supply for the bell shall be under 24-hour protection. Proper personnel for
maintenance or security of the system shall be able to disarm that area.
ANSI/UL 1023 Specications
Household Burglar-Alarm System Units
22.1 Audible Devices
At least one listed audible device (Ademco AB12M) rated to operate over the voltage rate of 11.7 VDC to 12.8 VDC
and rated at 85 DB minimum must be used.
22.2 Auxiliary Circuits
At least one burglary alarm initiating device shall be used on the system. If the voltage for the device is applied
by the control unit the burglary alarm initiating device shall be rated to operate over the range of 11.5 VDC to
12.7 VDC.
22.3 Bell Cutoff
TheBellCutofftimecannotbelessthanveminutes.SeetheXR500SeriesProgrammingGuide(LT-0679).
22.4 Entry Delay
Themaximumentrydelayusedmustnotbemorethan45seconds.SeetheXR500SeriesProgrammingGuide
(LT-0679).
22.5 Exit Delay
Themaximumexitdelayusedmustnotbemorethan60seconds.SeetheXR500SeriesProgrammingGuide
(LT-0679).
22.6 Weekly Test
The product should be tested weekly.
22.7 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as DAY for residential applications.