Installation guide
Digital Monitoring Products XR500 Series Installation Guide
4
IntRoduCtIon
3.2 Wiring Diagram
The XR500 Series diagram below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module follows in section 3.4.
Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715 compatibility
identifier: A
Maximum operating
range: 9.7 VDC to
14.0 VDC.
Class B (Style A).
See LT-0164 for a list of
approved 4-wire smoke
detectors and power
supervision relays.
WARNING: Incorrect
connections may cause
damage to the unit.
** For listed installations, total current combined from Auxiliary
(terminals 7, 11, 25, and 27) and Bell Power (terminal 5) cannot exceed:
1.3 Amp with 50 VA transformer, 1.0 Amp Max for Auxiliary Power
1.9 Amp with 56 VA transformer, 1.0 Amp Max for Auxiliary Power and 1.5 Amp Max for Bell
DMP Transformers
Model 327 – 16.5 VAC 50 VA
Class 2 Plug-in
Model 322 – 16 VAC 56 VA
Class 2 Wire-in
Secondary Power Supply
1.0 Amps Max. charging current.
Use only 12 VDC rechargeable
batteries. DMP Models 365, 366,
367, 368, or 369. Replace
batteries every 3 to 5 years.
Bell **
12 VDC
Minimum cutoff time 5 min.
1.5 Amp Max
Minimum voltage on Auxiliary output
to process Sensor trips is 10.2 VDC.
Auxiliary Power **
Total current combined from
terminals 7, 11, 25, and 27
1.5 Amp Max
10.2 VDC to 14.0 VDC
Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
For Standard Line
Security burglary
applications use
Ademco Model
AB12M bell and bell
housing.
Front and Rear
tamper protection
included with
Model 350A
Attack Resistant
Enclosure.
Bell cutoff time
range is 5 to 99
minutes, non-coded.
See the XR500 Series Installation Guide (LT-0681) for a complete list of
approved 2-wire smoke detectors for zones 9, 10, and 715 Zone
Expansion Module zones.
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GNDSMK GNDRED YEL GRNBLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+ Z9– Z10+ Z10–AC –BGND GNDGNDGND
K6 K7
Output 1Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
J23
J21
RS-232
Power
LED
J8
PROG
J4
Tamper
J16
Reset
Out1 Out2
Outputs 3-6
J11
3
4
5
6
J2
¼"
J1
Ethernet
R
L
X
Link LED
Activity LED
OVC
XR500 Series
Command Processor™
Panel
1k Ohm 1k Ohm1k Ohm
DISARM
ARM
Smoke
Detector
3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm
1k Ohm
Form C Relays (J2)
Output Color Code–Model 431 Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Annunciator Outputs (J11)
Output Color Code
Output 3 Red
Output 4 Yellow
Output 5 Green
Output 6 Black
AC Wiring must be in conduit and exit
out the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
Front
Tamper
Rear
Tamper
s
16 to 18 gauge wire
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
RED
BLACK
Cold Water
Pipe Earth
Ground
Bell
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
3.3k
Ohm
Resistor
3.3k
Ohm
Resistor
Zone Expander
Model 715
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Use Listed Power Supervision
Relay rated at 12 VDC.
1k Ohm
s
= Supervised Circuit
Zone
9
Zone
10
22 gauge minimum
22 gauge minimum
22 gauge minimum
22 gauge minimum
RED
YELLOW
GREEN
BLACK
1k Ohm 1k Ohm 1k Ohm
Zone Expander
Model 714
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
RED
YELLOW
GREEN
BLACK
RED
s
s
s
s s s s s
s
For listed installations, the Model
327 plug-in transformers shall be
installed in a DMP Model ES501
enclosure. The plug-in transformer
shall plug into a 120 VAC 60 Hz
outlet not controlled by a switch
and all
16 to 18 gauge wire
shall
run through conduit.
s
s
s
S S S S S S S S
S S S S
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
S S
S SS SS S
1k Ohm
Zone Expander
(up to 8 zones)
Model 712-8
19mA @ 12
VDC
S S
Zone
Expander
Model 711
7mA @ 12
VDC
1k
Ohm
s
Keyswitch Arming
can be connected
to any zone. See
LT-0681
s
s
s
s s
s s
s
TYPES OF SERVICE
Central Station DACT service may be provided.
Suitable for Remote Station PPU DACT Service.
Suitable for manual fire alarm, automatic fire
alarm, sprinkler supervisory, or water flow alarm.
Suitable for Standard or Encrypted Central Station
with NET communication.
DACT Central Station using 350A Attack Resistant
enclosure.
NFPA 72
This equipment should be installed in accordance with Chapter 11 of the National
Fire Alarm Code, ANSI/NFPA 72-2002, (National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269). Printed information describing proper
installation, operation, testing, maintenance, evacuation planning, and repair
service is to be provided with this equipment.
POWER LIMITED
All circuits on the Model XR500 Series comply with the requirements for inherent
power limitation and are Class 2 except the red battery wire and AC terminals.
NFPA 72 OPERATING INSTRUCTIONS
The operating instructions found on the last
page of LT-0681 must be located adjacent to
the control unit or keypad.
HOUSEHOLD FIRE WARNING
Recognized limited energy cable must be used
for connection of all initiating, indicating, and
supplementary devices.
WARNING
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM VERIFICATION
FEATURE THAT RESULTS IN DELAY OF THE SYSTEM ALARM SIGNAL FROM
THE INDICATED CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS
SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS. NO OTHER
SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
Verification
Zones
______
Control Unit
Delay
13.6 sec.
Smoke
Model
______
Detector
Delay
____sec.
In all applications where more than one wire
is under a terminal, the wire must be cut
and NOT looped around the screw terminal.
Zones 9, 10, and all
expanded zones are
suitable for Class B (as
applicable for the
initiating and signaling
line circuits per ANSI/UL
864 Table 48.2 or 48.3).
Installation limits under
local Authority Having
Jurisdiction (AHJ).
Using verification delays
on zones 9 and 10 is
optional. Use the
delays marked on the
smoke detectors.
Suitable for Bank Safe and Vault Service
with 350A Enclosure.
Suitable for Household Fire and Household
Burglary.
Suitable for Local, Police Station Connect,
Mercantile, and Proprietary with dialer
direct communication and 350A Enclosure.
Suitable for Proprietary, PPU, other
technologies, (iCOM – XR500 only), local.
SIA CP-01-2000 minimum system is
XR500, UL listed local Bell, and off
premise DACT communication to an
SCS-1R receiver plus listed compatible
keypads as indicated in the installation
guide.
Figure 1: XR500 Series Wiring Diagram