Installation Guide XR500 Series Command Processor™ Panel
MODEL XR500, XR500N, XR500E COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed and used properly in strict accordance with the manufacturer’s instructions, may cause interference with radio and television reception.
Table of Contents Product Specifications 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Power Supply..........................................................................1 Communication.......................................................................1 Panel Zones............................................................................1 Keypad Bus.............................................................................1 LX-Bus™.................................................................................
Table of Contents Smoke and Glassbreak Detector Output 9.1 9.2 Terminals 11 and 12..............................................................14 Current Rating.......................................................................14 Protection Zones 10.1 10.2 10.3 10.4 Terminals 13–24....................................................................15 Operational Parameters..........................................................15 Zone Response Time..................................................
Table of Contents 20.7 20.8 20.9 20.10 20.11 20.12 Listed Receivers....................................................................23 Power Supply Supervision......................................................23 Wireless Tamper....................................................................23 Wireless External Contact.......................................................23 Wireless Supervision Time......................................................23 Detect Wireless Jamming..................
Table of Contents ANSI/UL 365 Specifications 26.1 26.2 26.3 26.4 26.5 26.6 26.7 26.8 26.9 26.10 26.11 System Trouble Display..........................................................27 Entry Delay...........................................................................28 Exit Delay.............................................................................28 Bell.......................................................................................28 Bell Cutoff..........................................
Table of Contents ANSI/UL 985 NFPA 72 (Chapter 2) Specifications 31.1 31.2 31.3 31.4 31.5 31.6 31.7 31.8 Bell Output Definition.............................................................32 Audible Devices.....................................................................32 Auxiliary Circuits....................................................................32 Bell Cutoff.............................................................................32 Detect Wireless Jamming..............................
Introduction Product Specifications 1.1 Power Supply Transformer Input: Model 327, plug-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16.5 VAC 50 VA Model 322, wire-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA Standby Battery: 12 VDC, 1.0 Amps Max. charging current Models 365, 366, 367, 368, or 369 Replace every 3 to 5 years * Auxiliary: 12 VDC output at 1.5 Amp Max * Bell Output: 12 VDC at 1.
Introduction Panel Features 2.1 Description The DMP XR500 Series Command Processor™ Panel is a versatile 12 VDC, combined access control, burglary, and fire communicator panel with battery backup. The XR500 Series provides eight on-board burglary zones and two on-board 12 VDC Class B powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors, relays, or other latching devices.
Introduction 2.5 Encrypted Communications (XR500N/XR500E only) An XR500E panel communicates using AES Rijndael encryption. If you currently have an XR500N panel installed, you may contact DMP Customer Service with the panel serial number. The serial number(s) should be sent in writing via e-mail or fax. A separate feature key is sent for each panel to activate encrypted communications using the Feature Upgrade process. Encrypted communication cannot be enabled on a standard XR500 panel.
Introduction 3.2 Wiring Diagram The XR500 Series diagram below shows some of the accessory modules you can connect for use in various applications. A brief description of each module follows in section 3.4. TYPES OF SERVICE Central Station DACT service may be provided. NFPA 72 OPERATING INSTRUCTIONS The operating instructions found on the last page of LT-0681 must be located adjacent to the control unit or keypad.
Introduction 3.3 Lightning Protection Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR500 Series input and output circuits. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning Suppressors. 3.4 Accessory Devices Interface Adaptor and Interface Cards 461 Interface Adaptor Card Allows you to connect two or more expansion interface cards to the XR500 Series panel.
Introduction 3.4 Accessory Devices (continued) DMP Two-Way Wireless Devices (continued) * 1139 Bill Trap Provides a silent alarm option for retail and banking cash drawers. 1142BC Two-button Hold-up Belt Clip Transmitter Provides two-button hold-up operation with a belt clip. 1142 Two-button Hold-up Transmitter Provides permanently mounted under-the-counter two-button hold-up operation.
Installation Installation 4.1 Mounting the Enclosure The metal enclosure for the XR500 Series must be mounted in a secure, dry place to protect the panel from damage due to tampering or the elements. It is not necessary to remove the XR500 Series PCB when installing the enclosure. Figure 2 shows the mounting hole locations for the Model 350/350A Enclosures. Figure 3 shows the Model 341 Small Enclosure. Figure 4 shows the Model 352X panel cabinet and 352S shelf cabinet for multiple batteries.
Installation 56 VA Transformer Mounting Plate J3 Phone Line J4 Tamper J1 Ethernet Link LED Activity LED XR500 Series RS232 J23 Power LED 5 R L X 4 3 2 1 G 9 8 7 6 J22 LX-Bus RED J10 Output 1 OVC AC +B 1 2 3 Out2 –B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 8 9 10 11 12 13 14 K7 Outputs 3-6 AC J6 Expansion Slot Output 2 Out1 RED K6 J8 Z3 GND Z4 Z5 GND Z6 15 16 17 18 19 J16 Reset 20 21 Z7 GND Z8 Z9+ Z9– Z10+Z10– 22 23 24 25 26 27 28 Mounting for
Installation 4.3 Connecting LX-Bus and Keypad Bus Devices Several factors determine the DMP LX-Bus™ and keypad bus performance characteristics: the wire length and gauge used, the number of devices connected, and the voltage at each device. When planning an LX-Bus™ and keypad bus installation, keep in mind the following information: 1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do not use twisted pair or shielded wire for LX-Bus and keypad bus data circuits. 2.
Installation Secondary Power Supply 6.1 Battery Terminals 3 and 4 Connect the black battery lead to the negative battery terminal. The negative terminal connects to the enclosure ground internally through the XR500 Series circuit board. Connect the red battery lead to the battery positive terminal. Observe polarity when connecting the battery. You can add a second battery in parallel using the DMP Model 318 Dual Battery Harness.
Installation 6.8 XR500 Series Power Requirements During AC power failure, the XR500 Series panel and all connected auxiliary devices draw their power from the battery. All devices must be taken into consideration when calculating the battery standby capacity. The following table lists the XR500 Series panel power requirements.
Installation Standby Battery Power Calculations Standby Current Alarm Current 736P POPIT Interface Module Radionics Popex, POPITs, OctoPOPITs Qty _______ Qty _______ x 25mA ______ x ___mA ______ Qty _______ Qty _______ x x 25mA ______ ___mA ______ 738A Ademco Wireless Interface Module Qty _______ x 75mA ______ Qty _______ x 75mA ______ 710 Bus Splitter/Repeater Module Qty _______ x 30mA ______ Qty _______ x 30mA ______ 710F Fire Bus Splitter/Repeater Module Qty _______ x 40mA _____
Installation 6.9 Standby Battery Selection To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the Amp Hours Required calculation from section 6.8 XR500 Series Power Requirements, perform the following: 1. Select the desired standby hours required from the table below: 24, 60, or 72 hours 2. Select the desired battery size: Model 368 (12 VDC 4.5 Ah), Model 369 (12 VDC 7 Ah), Model 367 (12 VDC 7.7 Ah), Model 365 (12 VDC 9 Ah), Model 366 (12 VDC 18 Ah). 3.
Installation Bell Output 7.1 Terminals 5 and 6 Terminal 5 supplies positive 12 VDC to power alarm bells or horns. This output can be steady, pulsed, or temporal depending upon the Bell Action specified in Output Options. Terminal 6 is the ground reference for the bell circuit. This supervised output detects 1k Ohms or less as normal. The indicating appliance can supply this resistance.
Installation Protection Zones 10.1 Terminals 13–24 Zones 1 to 8 (terminals 13 to 24) on the XR500 Series panel are all grounded burglary zones. For programming purposes, the zone numbers are 1 through 8. Listed below are terminal 13 to 24 connection functions.
Installation 11.2 Compatible 2-Wire Smoke Detector Chart Manufacturer Model Detector ID Base Detection Systems DS230, DS230F B/A MB2W, MB2WL A 8.5-33 10 Detection Systems DS250, DS250TH B MB2W, MB2WL A 8.5-33 10/12 Detection Systems DS250HD B MB2W, MB2WL A 8.5-33 10 B/A MB2W, MB2WL A 8.5-33 17 8.
Installation Dry Contact Relay Outputs 12.1 Description The XR500 Series panel provides two auxiliary SPDT relays when equipped with two DMP Model 305 relays in sockets K6 (Output 1) and K7 (Output 2) and a Model 431 Output Harness on the J2 6-pin Header.
Installation J23 6-Pin Header 14.1 Description The XR500 Series Command Processor™ panel supports RS-232, LX-Bus, and DMP Wireless operation. Only one operation can function at a time. Install a jumper on one pair of J23 headers to indicate how the panel is programmed to operate. Refer to the table below when installing a jumper on J23. When a jumper is installed or moved on the 6-pin header, briefly reset the panel using the J16 jumper to activate the selected operation.
Installation 15.3 LX-Bus Interface Cards You can add one Interface Card (Model 481, 462N, 462P or 472) to the XR500 Series using J6 Interface Card Connector located on the board right edge. To add more than one Interface Card install a 461 Interface Adaptor Card using J6 Interface Card Connector on the board right edge. The 461 Adaptor Card allows you to install up to five Interface Cards. Refer to the 461 Installation Sheet (LT-0736). Each Interface card provides up to 100 LX-Bus Zones.
Installation 16.3 Direct iCOM Connection to J21 Use DMP Model 397 cable with a DB-9 female connector on one end and an RJ connector on the other end. Mount the iCOM in the panel enclosure. Refer to the iCOM Installation Guide (LT-0587). Plug the 397 cable DB-9 male connector end onto the XR500 Series panel J21 RS-232 connector. Plug the RJ connector into the iCOM J1 Network connector. Program the XR500 Series panel as needed. 16.
Installation 18.2 Description Connect the panel to the public telephone network by installing a DMP 356 RJ Cable between the panel J3 connector and the RJ31X or RJ38X phone jack. 18.3 J10 893A Connector Connect an 893A Dual Phone Line Module to J10 on the XR500 Series. Refer to the 893A Installation Sheet (LT‑0135) for complete information. 18.4 Notification The user must not repair registered terminal equipment. In case of trouble, immediately unplug the device from the telephone jack.
Installation Reset and Tamper Headers 19.1 J16 Reset Header The reset header is located just above the terminal strip on the right side of the circuit board and is used to reset the XR500 Series microprocessor. To reset the panel when first installing the system, install the reset jumper before applying power to the panel. After connecting the AC and battery, remove the reset jumper.
Compliance Universal Burglary Specifications 20.1 Introduction The programming and installation specifications contained in this section must be completed when installing the XR500 Series panel in accordance with any of the burglary standards. Additional specifications may be required by a particular standard. 20.2 Wiring All wiring must be in accordance with NEC, ANSI/NFPA 70, ANSI/UL 681, and ANSI/UL 827 for all burglary installations. All transformer wires must be installed in conduit. 20.
Compliance Area Information 21.1 Ownership The control unit system shall be under one ownership. 21.2 Annunciation The System shall be installed so that when arming any area from any keypad, the local bell shall annunciate. 21.3 Trouble Display The Status List programming shall be set to annunciate all trouble messages at all keypads. See the XR500 Series Programming Guide (LT-0679). 21.4 Closing Wait The Closing Wait option must be programmed YES.
Compliance ANSI/UL 1610 AND ANSI/UL 1076 Specifications Central-Station and Proprietary Burglar-Alarm Units 23.1 Opening/Closing Reports The Opening/Closing Reports option must be programmed as YES. See the XR500 Series Programming Guide (LT‑0679). 23.2 Closing Wait The Closing Wait option must be programmed YES. See the XR500 Series Programming Guide (LT-0679). 23.3 Entry Delay The maximum entry delay used must not be more than 60 seconds when using Model 350A Attack Resistant Housing.
Compliance 23.11 Model 463G CELL with Dialer Backup, Standard or Encrypted Line Security Standard or Encrypted Line Security is provided when programmed using CELL with DD (digital dialer) as a backup. XR500 cellular communication is used as primary with a 6 minute check-in when armed, and a random check-in over a 60 minute period when disarmed. The digital dialer sends a daily test signal and is backup.
Compliance ANSI/UL 636 Specifications Holdup Alarm Units 24.1 ANSI/UL 1610 Required The programming and installation specifications contained in this section must be completed in addition to ANSI/UL 1610 Specifications when installing a Model 1142 with a Model XR500 Series panel. 24.2 1100X Wireless Receiver The Model 1100X Wireless Receiver in conjunction with the Model 1142 Holdup Alarm Transmitter must be installed in the system. 24.
Compliance 26.2 Entry Delay The maximum entry delay used must not be more than 60 seconds when using Model 350A Attack housing. See the XR500 Series Programing Guide (LT-0679). 26.3 Exit Delay The maximum exit delay used must not be more than 60 seconds. See the XR500 Series Programming Guide (LT‑0679). 26.4 Bell A local audible signal appliance must be used such as Ademco AB12M bell and bell housing. 26.5 Bell Cutoff The Bell Cutoff time cannot be less than 15 minutes.
Compliance 26.12 Model 463G NET with CELL as Alternate Primary and Dialer Backup, Standard or Encrypted Line Security Standard or Encrypted Line Security is provided using NET communication with CELL as an alternate primary and with digital dialer as a backup. XR500 network communication is used as primary with a 6 minute check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and set to daily test.
Compliance 27.4 Mercantile Safe and Vault When the DMP Model 350A housing is used, the XR500 Series provides operation as a mercantile safe and vault alarm. Bell Supervision and wiring must be in accordance with ANSI/UL 681. When the XR500 Series is mounted outside the safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should be used. 27.5 Bell A local audible signal appliance must be used such as Ademco AB12M bell and bell housing. 27.
Compliance 29.3 Transformer A wire-in transformer should be used. Use the Model 322 wire-in 16 VAC 56 VA transformer or Model 327 plug-in 16 VAC 50 VA transformer installed inside an ES501 Enclosure with all wiring in conduit. The transformer must be mounted within 20 feet of the panel and connected by conduit. 29.4 End-of-Line Resistor The DMP Model 310 1k Ohm EOL resistor should be used on all 1k Ohm EOL fire zones. 29.
Compliance 30.3 Sprinkler Supervisory Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The last three characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual Phone Line Module must be used on all sprinkler supervisory systems. 30.4 DACT Systems Two phone lines must be used. The two phone lines cannot be ground start or party lines.
Compliance 31.5 Detect Wireless Jamming The Detect Wireless Jamming option must be programmed YES. See the XR500 Series Programming Guide (LT-0679). 31.6 Wireless External Contact When used, the External Contact of 1101 or 1102 must be programmed Normally Closed. See the XR500 Series Programing Guide (LT-0679). 31.7 Wireless Supervision Time The Zone Information Supervision Time must be 240 minutes. See the XR500 Series Programing Guide (LT-0679). 31.
Wiring Diagrams False Alarm Reduction Programmable Options * 34.1 Shipping Defaults and Recommended Programming for ANSI/SIA CP-01-2000 SIA CP-01 FEATURE PARAGRAPH # AND DESCRIPTION DMP XR500 PROGRAMMING GUIDE LT‑0679 SECTION # REQUIREMENT RANGE 4.2.2.1 Exit Time 15.2 Exit Delay Required 45 sec. - 250 sec. (Programmable) 4.2.2.2 Progress Annunciation 15.2 Exit Delay Allowed 4.2.2.3 Exit Time Restart 15.2 Exit Delay Required Option 4.2.2.
Wiring Diagrams False Alarm Reduction Programmable Options (continued) 34.2 Call Waiting (ANSI/SIA CP-01-2000) The Call Waiting default setting is disabled. To cancel the Call Waiting feature, program * (star) 7 0 P (pause), the standard telephone code prefix that cancels call waiting, into the telephone number string. Cancel Call Waiting for telephone lines that have Call Waiting operational on the telephone line. See the XR500 Series Programming Guide (LT‑0679).
Digital Monitoring Products 36 Notification Circuit Module DMP Model 865 25mA @12 VDC 1 AUX PWR 2 GND 3 Alarm In 4 Bell PWR In + 5 Bell PWR In 6 Bell Out A + 7 Bell Out A 8 Bell Out B + 9 Bell Out B 10 Bell Trouble 11 Bell Trouble 865 Module Normal/Silence Switch Power Supply Trouble Contacts N/C + Auxiliary Power Supply AUX PWR GND Alarm In Bell PWR In Bell Out + Bell Out Bell Trouble Bell Trouble 24 VDC 5 Amp Maximum 1 2 3 4 5 6 7 8 866 Module Normal/Silence Switch S S S S 1K EOL S S S
Wiring Diagrams 36.2 Multiple Notification Circuit Modules for Zoned Annunciation J4 Tamper J3 XR500 Series Command Processor™ Panel J1 J2 Output Header All outputs must be located within the same room as the control panel. J21 J23 R L X To additional Zone 1 Notification Circuit Modules. Install up to a maximum of twenty-five 866 Modules by using the relay outputs available on the XR500 Series panel.
Wiring Diagrams 36.
Wiring Diagrams 36.4 Cellular Backup Installation for Derived Channel Burglary The Secure-Com Cellular System must be connected to a separate power supply. Use only for supplementary (backup communication).
Wiring Diagrams 36.5 Derived Channel Installation Using Bosch D8122 XR500 Series Command Processor™ Panel J4 Tamper J3 Phone Line Form C Dry Contact Relays (J2) Output Color Code–Model 431 Harness Output 2 N/O Orange/White Output 2 Com White/Gray Output 2 N/C Violet/White Output 1 N/O Orange Output 1 Com Gray Output 1 N/C Violet J1 J21 Output Header J2 for K6 and K7 Dry Contact Relays. All outputs must be connected to devices located within the same room as the panel.
XR500 Series Installation Guide Green LED Red LED Silence BLO BLI Test Common + 12 VDC Rothenbuhler 5110 High Security Bell K3 R L X J23 J10 J22 RS-232 J21 J1 J4 Tamper K6 J2 1 3 4 Output 1 N/C Output 2 N/C 2 5 6 S 7 9 S 10 12 13 14 15 16 Output 1 Common 11 10K EOL DMP Model 308 Output 2 Common 8 J11 18 19 10K EOL DMP Model 308 17 20 J16 Reset J6 Interface Card Expansion Connector 24 25 26 27 28 Model 431 Output Harness S = Supervised Circuit 23 Z7 GND Z8 Z9+
Wiring Diagrams 36.7 LX-Bus™ Module Connection LX-Bus Expansion Interface Card DMP Models 481, 462N, 462P, 462FM, or 472 Model 867 Notification Module Normal/Silence Switch Ground Fault LED Bell Trouble LED Auxiliary Power Supply must be regulated (12 VDC Nominal), UL Listed for Fire Protective Signaling Service. Power Supplies must have battery backup and be power limited.
R L X J23 XR500 Series Installation Guide J10 J22 RS-232 J21 J1 J4 Tamper K6 J2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 J11 15 16 17 18 19 20 J16 Reset J6 Interface Card Expansion Connector 24 25 26 27 28 J2 1 2 3 4 +12 VDC { Relay 2 { Relay 3 { Relay 4 { Relay 1 Model 860 Relay Module Relay contact rating: 1 Amp @ 30 VDC, resistive 4-wire Harness Assembly RED YEL GRN BL K Auxiliary Power Supply must be regulated (12 VDC Nominal), UL Listed for Fire Protective Signaling S
Wiring Diagrams 36.
Revisions Revisions to This Document This section explains the changes that were made to this document during this revision. This section lists the date the change was made, the section number and heading, and a quick summary of the change. Ver. Section Number and Heading 1.03 23.10 Model 463G CELL Only, Standard Line Security 23.11 Model 463G CELL with Dialer Backup, Standard Line Security 23.12 Model 463G NET with CELL as Alternate Primary and Dialer Backup, Standard Line Security 23.
800-641-4282 INTRUSION • FIRE • ACCESS • NETWORKS www.dmp.