Installation guide
Digital Monitoring Products 7000 Series Keypad Installation Guide
2
7000 Series Keypad Installation Guide Digital Monitoring Products
3
Additional Power Supply
If the current draw for all keypads exceeds the panel output, you can provide additional current by adding a Model
505-12 auxiliary power supply. Connect all keypad black ground wires to the power supply negative terminal. Run
a jumper wire from the power supply negative terminal to the panel common ground terminal. Connect all keypad
power (+12 VDC) wires to the power supply positive terminal. Do NOT connect the power supply positive terminal to
any panel terminal. Refer to the 504-24 and 505-12 Power Supply Installation Guide (LT-0453) for more information.
Keypad Bus Monitor
For UL Listed re protective systems, the 893/893A Module must be installed in the XR500 Series or XR200 control
panel to monitor the keypad bus and sound an audible trouble whenever the keypad bus fails to operate. Refer to
the 893/893A Module Installation Sheet (LT-0135).
Card Readers
When a proximity credential is presented to an internal or external reader, a beep tone is heard and the Power and
Armed LEDs blink. This provides both an audible and visual acknowledgement of the credential read.
Internal Access Control Reader
The 7063 and 7073 keypads provide a built-in proximity card reader designed to read HID 1300 Series proximity
credentials.
Note: For UL Listed access
control applications, the keypad
must be installed within the
protected area.
External Access Control Reader
To accept Wiegand data input
from HID, DMP, or other external
card readers, connect a 12 VDC
external reader to the 7073
keypad. Connect the Red and
Black power wires from the reader
to the power wires from the panel.
These connect in parallel with the
keypad power wires. Connect the
Reader (Data 1) wire to the White
wire on the 5-wire keypad harness.
Connect the Reader (Data 0) wire
to the Green/White wire on the
5-wire keypad harness.
7073 Door Strike Relay Specications
The 7073 keypad provides one internal Form C single pole, double throw (SPDT) relay for controlling door strikes
or magnetic locks. Three wires on the 5-wire harness, Violet (N/C), Gray (Com), and Orange (N/O), allow you to
connect devices to the relay. The Form C relay draws up to 15mA of current and its contacts are rated for 1 Amp at
30 VDC maximum.
Wiring the 333 Suppressor
One Model 333 Suppressor is included with the 7073
keypad. Refer to Figure 3 and install the suppressor
across the 5-wire output/reader harness Common (C)
and Normally Open (N/O) or Normally Closed (N/C).
If the device being controlled by the relay is
connected to the N/O and C wires, install the
suppressor on the N/O and C wires. If the device is
connected to the N/C and C wires, install the 333
Suppressor on N/C and C wires.
1K EOL
1K EOL
1K EOL
1K EOL
Green/White – Connect Reader Data 0
White – Connect Reader Data 1
Orange – Door Strike Normally Ope
n
Gray
– Door Strike Common
Violet
– Door Strike Normally Closed
Yellow/White
White/Yello
w
Orange White
White/Orange
Red/White
White/Re
d
Brown/White
White/Brow
n
Black – Ground
Green
– Receive Data
Yellow – Send Data
Red – Keypad Power
– Zone 4
– Zone 3 Request to Exit (option)
– Zone 2 Door Contact
(option)
– Zone 1 7/0 Panic (option)
To Keypad Bus
External Card
Reader
Figure 2: 12 VDC Reader Wiring for 7073 Keypad
Figure 3: 7073 5-wire Harness and Suppressor Installation